EB-445AC6-B01 C
22.50 kW
Defrost: None
Product code: EB-345AE6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 13,465 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 62.4 m² |
| Inner volume | 15.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 113 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EB-345AE6-B01 C | None |
|---|---|
| EB-345AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.28 | 9.55 | 9.79 | 9.97 | 10.03 | 9.98 | 9.86 | 10.09 | 10.73 | 11.61 | 11.31 | 11.21 | 11.08 | 10.82 |
| 5 | 11.54 | 12.05 | 12.52 | 12.93 | 13.19 | 13.31 | 13.32 | 13.59 | 14.44 | 15.64 | 15.19 | 15.02 | 14.78 | 14.42 |
| 6 | 13.60 | 14.36 | 14.98 | 15.60 | 16.00 | 16.23 | 16.30 | 16.59 | 17.64 | 19.17 | 18.70 | 18.52 | 18.25 | 17.82 |
| 7 | 15.40 | 16.46 | 17.43 | 18.28 | 18.86 | 19.20 | 19.31 | 19.64 | 20.87 | 22.69 | 22.13 | 21.91 | 21.53 | 20.95 |
| 8 | 17.04 | 18.42 | 19.70 | 20.83 | 21.62 | 22.01 | 22.27 | 22.65 | 24.09 | 26.19 | 25.57 | 25.30 | 24.89 | 24.12 |
| 9 | ≈ 18.51 | 20.23 | 21.85 | 23.10 | 24.13 | 24.83 | 25.22 | 25.71 | 27.35 | 29.74 | 29.10 | 28.79 | 28.29 | 27.35 |
| 10 | ≈ 19.82 | 21.90 | 23.57 | 25.38 | 26.69 | 27.60 | 28.15 | 28.76 | 30.61 | 33.31 | 32.64 | 32.30 | 31.71 | 30.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 32.640 |
| SC2 | 0 | 8 | 22.654 |
| SC3 | -18 | 7 | 18.540 |
| SC4 | -25 | 6 | 14.979 |
| SC5 | -34 | 6 | 13.778 |
| A | 2317 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 1985 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2317 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.