EB-345AE6-B01 C
22.65 kW
Defrost: None
Product code: EB-440AE7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 12,920 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 72.6 m² |
| Inner volume | 20.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 129 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EB-440AE7-B01 C | None |
|---|---|
| EB-440AE7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.27 | 9.71 | 10.11 | 10.45 | 10.66 | 10.75 | 10.74 | 10.92 | 11.61 | 12.59 | 12.28 | 12.17 | 12.02 | 11.80 |
| 5 | 11.30 | 12.01 | 12.66 | 13.24 | 13.65 | 13.90 | 14.04 | 14.30 | 15.22 | 16.57 | 16.24 | 16.11 | 15.89 | 15.52 |
| 6 | 13.05 | 14.05 | 14.98 | 15.81 | 16.41 | 16.81 | 17.04 | 17.36 | 18.48 | 20.13 | 19.73 | 19.57 | 19.32 | 18.89 |
| 7 | 14.79 | 16.09 | 17.29 | 18.38 | 19.18 | 19.74 | 20.08 | 20.44 | 21.76 | 23.64 | 23.22 | 23.03 | 22.73 | 22.20 |
| 8 | ≈ 16.23 | 17.84 | 19.38 | 20.77 | 21.81 | 22.42 | 22.93 | 23.43 | 24.97 | 27.23 | 26.76 | 26.55 | 26.21 | 25.55 |
| 9 | ≈ 17.51 | 19.45 | 21.33 | 22.76 | 24.15 | 25.13 | 25.81 | 26.45 | 28.21 | 30.79 | 30.35 | 30.12 | 29.73 | 28.94 |
| 10 | ≈ 12.82 | ≈ 20.91 | 23.14 | 24.92 | 26.54 | 27.78 | 28.65 | 29.45 | 31.43 | 34.34 | 33.91 | 33.67 | 33.24 | 32.38 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.912 |
| SC2 | 0 | 8 | 23.431 |
| SC3 | -18 | 7 | 18.728 |
| SC4 | -25 | 6 | 14.982 |
| SC5 | -34 | 6 | 13.273 |
| A | 2967 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 2635 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2967 mm |
|---|---|
| Width | 520 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.