EB-420AC7-B05 C
3.45 kW
Defrost: None
Product code: EB-420AB4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,734 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 17.2 m² |
| Inner volume | 3.0 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 4 |
|---|---|
| Diameter | 200 mm |
| Speed | 1,300 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 39.0 dB(A) |
|---|---|
| Sound power | 61.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EB-420AB4-B05 C | None |
|---|---|
| EB-420AB4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.41 | 1.46 | 1.51 | 1.55 | 1.58 | 1.60 | 1.60 | 1.62 | 1.72 | 1.87 | 1.83 | 1.82 | 1.80 | 1.77 |
| 5 | 1.73 | 1.82 | 1.90 | 1.98 | 2.03 | 2.06 | 2.08 | 2.11 | 2.24 | 2.44 | 2.39 | 2.37 | 2.34 | 2.29 |
| 6 | 2.01 | 2.14 | 2.25 | 2.36 | 2.44 | 2.49 | 2.53 | 2.57 | 2.73 | 2.98 | 2.93 | 2.91 | 2.88 | 2.82 |
| 7 | 2.29 | 2.45 | 2.61 | 2.74 | 2.84 | 2.91 | 2.97 | 3.02 | 3.21 | 3.50 | 3.44 | 3.42 | 3.38 | 3.31 |
| 8 | 2.52 | 2.73 | 2.93 | 3.11 | 3.24 | 3.34 | 3.41 | 3.46 | 3.69 | 4.01 | 3.95 | 3.93 | 3.88 | 3.81 |
| 9 | ≈ 2.73 | 2.99 | 3.23 | 3.45 | 3.63 | 3.73 | 3.82 | 3.90 | 4.16 | 4.54 | 4.47 | 4.44 | 4.40 | 4.31 |
| 10 | ≈ 2.92 | 3.22 | 3.52 | 3.79 | 3.97 | 4.13 | 4.24 | 4.34 | 4.63 | 5.06 | 5.00 | 4.97 | 4.91 | 4.82 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.996 |
| SC2 | 0 | 8 | 3.463 |
| SC3 | -18 | 7 | 2.789 |
| SC4 | -25 | 6 | 2.254 |
| SC5 | -34 | 6 | 2.039 |
| A | 1757 mm |
|---|---|
| B | 490 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 368 mm |
| E2 | 350 mm |
| E | 1435 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1757 mm |
|---|---|
| Width | 490 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.