EB-425AA6-B05 C
3.45 kW
Defrost: None
Product code: EB-420AC7-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,726 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 14.5 m² |
| Inner volume | 3.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 4 |
|---|---|
| Diameter | 200 mm |
| Speed | 1,300 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 39.0 dB(A) |
|---|---|
| Sound power | 61.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EB-420AC7-B05 C | None |
|---|---|
| EB-420AC7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.50 | 1.49 | 1.50 | 1.50 | 1.51 | 1.50 | 1.50 | 1.51 | 1.60 | 1.73 | 1.69 | 1.68 | 1.66 | 1.63 |
| 5 | 1.90 | 1.91 | 1.93 | 1.95 | 1.96 | 1.96 | 1.96 | 1.97 | 2.09 | 2.26 | 2.20 | 2.18 | 2.15 | 2.11 |
| 6 | 2.29 | 2.32 | 2.36 | 2.40 | 2.42 | 2.44 | 2.44 | 2.45 | 2.60 | 2.81 | 2.74 | 2.72 | 2.68 | 2.61 |
| 7 | 2.66 | 2.72 | 2.79 | 2.85 | 2.89 | 2.92 | 2.93 | 2.94 | 3.12 | 3.38 | 3.30 | 3.27 | 3.22 | 3.14 |
| 8 | 3.02 | 3.11 | 3.21 | 3.30 | 3.36 | 3.40 | 3.42 | 3.45 | 3.66 | 3.97 | 3.88 | 3.84 | 3.78 | 3.69 |
| 9 | 3.34 | 3.46 | 3.59 | 3.71 | 3.80 | 3.86 | 3.90 | 3.94 | 4.19 | 4.55 | 4.46 | 4.42 | 4.35 | 4.25 |
| 10 | 3.64 | 3.80 | 3.97 | 4.11 | 4.22 | 4.30 | 4.35 | 4.41 | 4.69 | 5.09 | 5.00 | 4.96 | 4.90 | 4.79 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.000 |
| SC2 | 0 | 8 | 3.447 |
| SC3 | -18 | 7 | 2.870 |
| SC4 | -25 | 6 | 2.357 |
| SC5 | -34 | 6 | 2.297 |
| A | 1757 mm |
|---|---|
| B | 490 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 368 mm |
| E2 | 350 mm |
| E | 1435 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1757 mm |
|---|---|
| Width | 490 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.