EB-230AC4-B05 C
4.22 kW
Defrost: None
Product code: EB-420AE7-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,628 m³/h |
|---|---|
| Air throw | 3 m |
| External surface | 21.7 m² |
| Inner volume | 5.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 39 kg |
| Quantity | 4 |
|---|---|
| Diameter | 200 mm |
| Speed | 1,300 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 39.0 dB(A) |
|---|---|
| Sound power | 61.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø22 |
| EB-420AE7-B05 C | None |
|---|---|
| EB-420AE7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.89 | 1.90 | 1.92 | 1.95 | 1.96 | 1.96 | 1.96 | 1.98 | 2.10 | 2.28 | 2.23 | 2.21 | 2.18 | 2.14 |
| 5 | 2.34 | 2.38 | 2.43 | 2.47 | 2.50 | 2.51 | 2.51 | 2.53 | 2.69 | 2.91 | 2.84 | 2.81 | 2.77 | 2.70 |
| 6 | 2.78 | 2.85 | 2.93 | 3.00 | 3.04 | 3.07 | 3.07 | 3.10 | 3.29 | 3.57 | 3.48 | 3.44 | 3.38 | 3.29 |
| 7 | 3.19 | 3.30 | 3.41 | 3.52 | 3.59 | 3.63 | 3.64 | 3.67 | 3.90 | 4.23 | 4.12 | 4.08 | 4.01 | 3.90 |
| 8 | 3.57 | 3.73 | 3.88 | 4.02 | 4.12 | 4.18 | 4.21 | 4.25 | 4.51 | 4.89 | 4.78 | 4.73 | 4.65 | 4.52 |
| 9 | 3.92 | 4.13 | 4.32 | 4.50 | 4.63 | 4.71 | 4.76 | 4.82 | 5.12 | 5.56 | 5.44 | 5.38 | 5.30 | 5.14 |
| 10 | 4.25 | 4.51 | 4.75 | 4.97 | 5.12 | 5.23 | 5.30 | 5.36 | 5.70 | 6.19 | 6.07 | 6.01 | 5.92 | 5.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.065 |
| SC2 | 0 | 8 | 4.252 |
| SC3 | -18 | 7 | 3.548 |
| SC4 | -25 | 6 | 2.925 |
| SC5 | -34 | 6 | 2.796 |
| A | 1757 mm |
|---|---|
| B | 490 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 368 mm |
| E2 | 350 mm |
| E | 1435 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø22 |
| Length | 1757 mm |
|---|---|
| Width | 490 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.