EB-335AC7-B01 C
10.82 kW
Defrost: Electric
Product code: EB-430AE6-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,644 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 35.8 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.3 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430AE6-B01 C | None |
|---|---|
| EB-430AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.75 | 4.77 | 4.80 | 4.84 | 4.84 | 4.81 | 4.76 | 4.84 | 5.15 | 5.58 | 5.44 | 5.39 | 5.33 | 5.23 |
| 5 | 5.97 | 6.07 | 6.18 | 6.28 | 6.31 | 6.30 | 6.25 | 6.32 | 6.70 | 7.26 | 7.03 | 6.95 | 6.83 | 6.65 |
| 6 | 7.13 | 7.34 | 7.54 | 7.72 | 7.81 | 7.83 | 7.79 | 7.86 | 8.33 | 9.02 | 8.73 | 8.62 | 8.45 | 8.18 |
| 7 | 8.17 | 8.47 | 8.77 | 9.03 | 9.20 | 9.29 | 9.30 | 9.40 | 9.97 | 10.82 | 10.49 | 10.35 | 10.14 | 9.78 |
| 8 | 9.20 | 9.61 | 9.96 | 10.32 | 10.54 | 10.67 | 10.71 | 10.83 | 11.48 | 12.44 | 12.12 | 11.97 | 11.75 | 11.35 |
| 9 | 10.11 | 10.65 | 11.16 | 11.61 | 11.90 | 12.05 | 12.12 | 12.26 | 13.01 | 14.09 | 13.73 | 13.56 | 13.30 | 12.82 |
| 10 | 10.95 | 11.64 | 12.28 | 12.84 | 13.22 | 13.45 | 13.55 | 13.70 | 14.54 | 15.75 | 15.36 | 15.17 | 14.87 | 14.30 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.355 |
| SC2 | 0 | 8 | 10.825 |
| SC3 | -18 | 7 | 9.111 |
| SC4 | -25 | 6 | 7.539 |
| SC5 | -34 | 6 | 7.186 |
| A | 2037 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1715 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2037 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.