EB-430AE4-B05 C
9.56 kW
Defrost: Electric
Product code: EB-430AE6-B05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,963 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 35.8 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430AE6-B05 C | None |
|---|---|
| EB-430AE6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.29 | 4.29 | 4.31 | 4.33 | 4.33 | 4.30 | 4.24 | 4.34 | 4.62 | 5.02 | 4.89 | 4.85 | 4.80 | 4.73 |
| 5 | 5.40 | 5.46 | 5.53 | 5.60 | 5.62 | 5.60 | 5.53 | 5.61 | 5.95 | 6.45 | 6.25 | 6.17 | 6.06 | 5.89 |
| 6 | 6.47 | 6.61 | 6.75 | 6.88 | 6.94 | 6.94 | 6.88 | 6.94 | 7.35 | 7.96 | 7.68 | 7.58 | 7.42 | 7.16 |
| 7 | 7.47 | 7.70 | 7.93 | 8.14 | 8.26 | 8.29 | 8.24 | 8.31 | 8.79 | 9.51 | 9.19 | 9.05 | 8.85 | 8.53 |
| 8 | 8.38 | 8.71 | 9.02 | 9.30 | 9.46 | 9.54 | 9.54 | 9.64 | 10.22 | 11.06 | 10.72 | 10.56 | 10.33 | 9.94 |
| 9 | 9.30 | 9.72 | 10.12 | 10.45 | 10.66 | 10.78 | 10.80 | 10.91 | 11.56 | 12.50 | 12.15 | 11.98 | 11.74 | 11.33 |
| 10 | 10.10 | 10.65 | 11.16 | 11.59 | 11.88 | 12.02 | 12.06 | 12.19 | 12.91 | 13.96 | 13.57 | 13.39 | 13.12 | 12.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.569 |
| SC2 | 0 | 8 | 9.639 |
| SC3 | -18 | 7 | 8.196 |
| SC4 | -25 | 6 | 6.753 |
| SC5 | -34 | 6 | 6.507 |
| A | 2037 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1715 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2037 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.