EB-430BC7-B01 C
8.29 kW
Defrost: Electric
Product code: EB-430BC6-B05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,960 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 28.4 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 56 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BC6-B05 C | None |
|---|---|
| EB-430BC6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.58 | 3.51 | 3.47 | 3.46 | 3.43 | 3.39 | 3.35 | 3.40 | 3.61 | 3.90 | 3.81 | 3.78 | 3.73 | 3.66 |
| 5 | 4.66 | 4.61 | 4.59 | 4.59 | 4.57 | 4.53 | 4.48 | 4.51 | 4.78 | 5.17 | 5.02 | 4.97 | 4.91 | 4.81 |
| 6 | 5.73 | 5.73 | 5.76 | 5.79 | 5.79 | 5.75 | 5.69 | 5.72 | 6.06 | 6.54 | 6.33 | 6.26 | 6.15 | 5.99 |
| 7 | 6.78 | 6.85 | 6.93 | 7.01 | 7.04 | 7.03 | 6.97 | 7.00 | 7.40 | 8.00 | 7.74 | 7.64 | 7.49 | 7.26 |
| 8 | 7.75 | 7.89 | 8.04 | 8.21 | 8.31 | 8.33 | 8.29 | 8.32 | 8.81 | 9.52 | 9.22 | 9.10 | 8.92 | 8.63 |
| 9 | 8.64 | 8.85 | 9.08 | 9.30 | 9.43 | 9.51 | 9.53 | 9.61 | 10.19 | 11.04 | 10.75 | 10.60 | 10.39 | 10.04 |
| 10 | 9.54 | 9.83 | 10.12 | 10.37 | 10.55 | 10.66 | 10.70 | 10.80 | 11.45 | 12.41 | 12.11 | 11.97 | 11.77 | 11.42 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.105 |
| SC2 | 0 | 8 | 8.321 |
| SC3 | -18 | 7 | 7.032 |
| SC4 | -25 | 6 | 5.755 |
| SC5 | -34 | 6 | 5.739 |
| A | 2357 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.