EB-245AC7-B07 C
11.19 kW
Defrost: Electric
Product code: EB-430BE7-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,123 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 37.2 m² |
| Inner volume | 10.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 68 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.2 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BE7-B01 C | None |
|---|---|
| EB-430BE7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.81 | 4.86 | 4.92 | 4.98 | 4.99 | 4.98 | 4.94 | 5.01 | 5.32 | 5.76 | 5.61 | 5.56 | 5.49 | 5.40 |
| 5 | 6.02 | 6.16 | 6.31 | 6.44 | 6.51 | 6.52 | 6.49 | 6.56 | 6.96 | 7.53 | 7.32 | 7.23 | 7.11 | 6.92 |
| 6 | 7.15 | 7.42 | 7.67 | 7.90 | 8.03 | 8.09 | 8.09 | 8.17 | 8.66 | 9.39 | 9.12 | 9.01 | 8.85 | 8.59 |
| 7 | 8.16 | 8.54 | 8.89 | 9.21 | 9.43 | 9.56 | 9.61 | 9.73 | 10.33 | 11.22 | 10.95 | 10.84 | 10.64 | 10.31 |
| 8 | 9.17 | 9.66 | 10.12 | 10.50 | 10.78 | 10.97 | 11.06 | 11.20 | 11.90 | 12.91 | 12.62 | 12.49 | 12.28 | 11.93 |
| 9 | 10.04 | 10.68 | 11.27 | 11.79 | 12.16 | 12.40 | 12.51 | 12.68 | 13.47 | 14.62 | 14.30 | 14.15 | 13.92 | 13.51 |
| 10 | 10.84 | 11.64 | 12.38 | 13.02 | 13.49 | 13.80 | 13.98 | 14.18 | 15.06 | 16.31 | 15.98 | 15.81 | 15.55 | 15.09 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.975 |
| SC2 | 0 | 8 | 11.202 |
| SC3 | -18 | 7 | 9.307 |
| SC4 | -25 | 6 | 7.667 |
| SC5 | -34 | 6 | 7.219 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.