EB-445AC4-B01 C
26.00 kW
Defrost: None
Product code: EB-440AE4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 12,076 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 115.1 m² |
| Inner volume | 20.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 130 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EB-440AE4-B01 C | None |
|---|---|
| EB-440AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.47 | 11.17 | 11.79 | 12.33 | 12.69 | 12.91 | 12.97 | 13.32 | 14.20 | 15.45 | 15.12 | 15.00 | 14.82 | 14.57 |
| 5 | 12.48 | 13.49 | 14.42 | 15.24 | 15.82 | 16.17 | 16.34 | 16.74 | 17.84 | 19.44 | 19.04 | 18.88 | 18.64 | 18.24 |
| 6 | 14.44 | 15.78 | 17.03 | 18.14 | 18.95 | 19.48 | 19.71 | 20.17 | 21.48 | 23.33 | 22.84 | 22.63 | 22.30 | 21.74 |
| 7 | 16.04 | 17.75 | 19.38 | 20.84 | 21.95 | 22.52 | 22.96 | 23.51 | 25.05 | 27.31 | 26.73 | 26.48 | 26.07 | 25.35 |
| 8 | 17.00 | 19.53 | 21.56 | 23.15 | 24.56 | 25.57 | 26.21 | 26.89 | 28.66 | 31.26 | 30.68 | 30.38 | 29.91 | 29.02 |
| 9 | not rated | 21.14 | 22.96 | 25.48 | 27.23 | 28.54 | 29.39 | 30.24 | 32.26 | 35.19 | 34.62 | 34.29 | 33.76 | 32.76 |
| 10 | not rated | 22.55 | 25.08 | 27.64 | 29.77 | 31.40 | 32.51 | 33.54 | 35.81 | 39.12 | 38.55 | 38.21 | 37.63 | 36.52 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 38.550 |
| SC2 | 0 | 8 | 26.890 |
| SC3 | -18 | 7 | 21.330 |
| SC4 | -25 | 6 | 17.031 |
| SC5 | -34 | 6 | 14.732 |
| A | 2967 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2967 mm |
|---|---|
| Width | 520 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.