EB-440AE6-B01 C
24.48 kW
Defrost: None
Product code: EB-345AE4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 12,556 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 86.3 m² |
| Inner volume | 15.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 114 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| EB-345AE4-B01 C | None |
|---|---|
| EB-345AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.33 | 10.79 | 11.19 | 11.50 | 11.65 | 11.66 | 11.54 | 11.90 | 12.68 | 13.76 | 13.44 | 13.34 | 13.20 | 13.01 |
| 5 | 12.56 | 13.28 | 13.92 | 14.47 | 14.82 | 14.98 | 14.99 | 15.37 | 16.38 | 17.82 | 17.40 | 17.25 | 17.04 | 16.71 |
| 6 | 14.70 | 15.71 | 16.63 | 17.42 | 17.94 | 18.17 | 18.24 | 18.63 | 19.82 | 21.56 | 21.00 | 20.77 | 20.44 | 19.90 |
| 7 | 16.53 | 17.89 | 19.14 | 20.23 | 20.98 | 21.41 | 21.46 | 21.89 | 23.27 | 25.29 | 24.62 | 24.33 | 23.90 | 23.15 |
| 8 | ≈ 18.17 | 19.90 | 21.52 | 22.75 | 23.76 | 24.39 | 24.68 | 25.19 | 26.78 | 29.11 | 28.36 | 28.02 | 27.46 | 26.49 |
| 9 | ≈ 19.62 | 21.74 | 23.52 | 25.28 | 26.56 | 27.43 | 27.88 | 28.49 | 30.30 | 32.93 | 32.14 | 31.74 | 31.08 | 29.92 |
| 10 | ≈ 19.95 | ≈ 23.40 | 25.54 | 27.67 | 29.27 | 30.40 | 31.04 | 31.78 | 33.81 | 36.77 | 35.94 | 35.48 | 34.74 | 33.40 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 35.937 |
| SC2 | 0 | 8 | 25.188 |
| SC3 | -18 | 7 | 20.568 |
| SC4 | -25 | 6 | 16.631 |
| SC5 | -34 | 6 | 14.929 |
| A | 2317 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 1985 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2317 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.