ED-A-A-325BC6-B24 C
2.49 kW
Defrost: None
Product code: ED-A-A-325AC6-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,525 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 7.5 m² |
| Inner volume | 2.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 15 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 59.7 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-A-A-325AC6-B24 C | None |
|---|---|
| ED-A-A-325AC6-B24 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.99 | 0.96 | 0.95 | 0.94 | 0.93 | 0.91 | 0.89 | 0.91 | 0.97 | 1.04 | 1.02 | 1.01 | 1.00 | 0.97 |
| 5 | 1.30 | 1.28 | 1.27 | 1.26 | 1.25 | 1.23 | 1.21 | 1.22 | 1.29 | 1.39 | 1.34 | 1.33 | 1.31 | 1.28 |
| 6 | 1.61 | 1.60 | 1.60 | 1.60 | 1.60 | 1.58 | 1.55 | 1.56 | 1.65 | 1.77 | 1.71 | 1.68 | 1.64 | 1.59 |
| 7 | 1.91 | 1.92 | 1.94 | 1.95 | 1.95 | 1.94 | 1.91 | 1.91 | 2.02 | 2.18 | 2.10 | 2.06 | 2.01 | 1.94 |
| 8 | 2.20 | 2.23 | 2.27 | 2.30 | 2.31 | 2.31 | 2.28 | 2.29 | 2.42 | 2.60 | 2.51 | 2.47 | 2.41 | 2.31 |
| 9 | 2.48 | 2.53 | 2.59 | 2.65 | 2.67 | 2.68 | 2.66 | 2.67 | 2.82 | 3.04 | 2.93 | 2.89 | 2.82 | 2.70 |
| 10 | 2.73 | 2.81 | 2.89 | 2.96 | 3.00 | 3.03 | 3.03 | 3.05 | 3.23 | 3.48 | 3.37 | 3.32 | 3.24 | 3.11 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.366 |
| SC2 | 0 | 8 | 2.286 |
| SC3 | -18 | 7 | 1.954 |
| SC4 | -25 | 6 | 1.600 |
| SC5 | -34 | 6 | 1.606 |
| A | 570 mm |
|---|---|
| B | 1200 mm |
| C | 150 mm |
| E | 970 mm |
| D | 300 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 570 mm |
|---|---|
| Width | 1200 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.