ED-A-A-325BC6-B24 C
2.49 kW
Defrost: None
Product code: ED-A-A-325CD6-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,410 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 9.6 m² |
| Inner volume | 3.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 18 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 59.7 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| ED-A-A-325CD6-B24 C | None |
|---|---|
| ED-A-A-325CD6-B24 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.17 | 1.17 | 1.17 | 1.18 | 1.18 | 1.17 | 1.15 | 1.18 | 1.25 | 1.35 | 1.32 | 1.31 | 1.29 | 1.27 |
| 5 | 1.49 | 1.50 | 1.52 | 1.54 | 1.54 | 1.54 | 1.52 | 1.54 | 1.63 | 1.77 | 1.71 | 1.69 | 1.66 | 1.61 |
| 6 | 1.79 | 1.83 | 1.86 | 1.90 | 1.92 | 1.92 | 1.90 | 1.92 | 2.03 | 2.20 | 2.13 | 2.10 | 2.05 | 1.98 |
| 7 | 2.08 | 2.14 | 2.20 | 2.26 | 2.29 | 2.30 | 2.29 | 2.31 | 2.45 | 2.65 | 2.56 | 2.53 | 2.47 | 2.38 |
| 8 | 2.35 | 2.44 | 2.53 | 2.61 | 2.66 | 2.68 | 2.68 | 2.71 | 2.87 | 3.10 | 3.01 | 2.97 | 2.90 | 2.79 |
| 9 | 2.60 | 2.72 | 2.84 | 2.94 | 3.01 | 3.05 | 3.06 | 3.10 | 3.29 | 3.56 | 3.46 | 3.41 | 3.34 | 3.21 |
| 10 | 2.83 | 2.98 | 3.13 | 3.26 | 3.35 | 3.40 | 3.42 | 3.47 | 3.68 | 3.99 | 3.89 | 3.84 | 3.77 | 3.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.891 |
| SC2 | 0 | 8 | 2.708 |
| SC3 | -18 | 7 | 2.274 |
| SC4 | -25 | 6 | 1.862 |
| SC5 | -34 | 6 | 1.798 |
| A | 570 mm |
|---|---|
| B | 1200 mm |
| C | 150 mm |
| E | 970 mm |
| D | 300 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 570 mm |
|---|---|
| Width | 1200 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.