ED-DP-340AC4-B22 C
15.47 kW
Defrost: None
Product code: ED-DP-245AC4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,154 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 64.9 m² |
| Inner volume | 14.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 120 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-245AC4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.53 | 6.52 | 6.54 | 6.57 | 6.56 | 6.51 | 6.45 | 6.55 | 6.96 | 7.53 | 7.36 | 7.30 | 7.22 | 7.11 |
| 5 | 8.35 | 8.41 | 8.53 | 8.63 | 8.65 | 8.62 | 8.53 | 8.62 | 9.15 | 9.89 | 9.62 | 9.52 | 9.38 | 9.19 |
| 6 | 10.06 | 10.32 | 10.56 | 10.76 | 10.85 | 10.84 | 10.76 | 10.84 | 11.49 | 12.42 | 12.03 | 11.89 | 11.67 | 11.34 |
| 7 | 11.59 | 12.01 | 12.40 | 12.75 | 12.96 | 13.07 | 13.06 | 13.15 | 13.92 | 15.06 | 14.60 | 14.41 | 14.14 | 13.69 |
| 8 | 12.97 | 13.57 | 14.05 | 14.54 | 14.85 | 15.02 | 15.08 | 15.23 | 16.16 | 17.53 | 17.09 | 16.90 | 16.61 | 16.14 |
| 9 | 14.25 | 14.97 | 15.70 | 16.33 | 16.75 | 17.00 | 17.10 | 17.29 | 18.35 | 19.89 | 19.40 | 19.18 | 18.85 | 18.28 |
| 10 | 15.42 | 16.36 | 17.28 | 18.08 | 18.63 | 18.97 | 19.14 | 19.37 | 20.55 | 22.28 | 21.75 | 21.50 | 21.12 | 20.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.746 |
| SC2 | 0 | 8 | 15.233 |
| SC3 | -18 | 7 | 12.847 |
| SC4 | -25 | 6 | 10.557 |
| SC5 | -34 | 6 | 10.129 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.