ED-DP-240AE4-B22 C
11.61 kW
Defrost: None
Product code: ED-DP-245AC7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,616 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 40.4 m² |
| Inner volume | 13.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 109 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.2 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-245AC7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.62 | 4.63 | 4.64 | 4.65 | 4.63 | 4.58 | 4.52 | 4.56 | 4.83 | 5.21 | 5.06 | 5.00 | 4.92 | 4.80 |
| 5 | 5.93 | 6.04 | 6.14 | 6.22 | 6.24 | 6.22 | 6.16 | 6.19 | 6.55 | 7.07 | 6.86 | 6.78 | 6.68 | 6.52 |
| 6 | 7.22 | 7.45 | 7.66 | 7.84 | 7.91 | 7.94 | 7.90 | 7.95 | 8.42 | 9.09 | 8.81 | 8.71 | 8.56 | 8.32 |
| 7 | 8.35 | 8.71 | 9.05 | 9.35 | 9.55 | 9.67 | 9.71 | 9.75 | 10.34 | 11.20 | 10.88 | 10.76 | 10.57 | 10.27 |
| 8 | 9.33 | 9.84 | 10.31 | 10.67 | 10.96 | 11.15 | 11.25 | 11.39 | 12.10 | 13.15 | 12.86 | 12.75 | 12.56 | 12.27 |
| 9 | 10.24 | 10.91 | 11.45 | 11.99 | 12.38 | 12.64 | 12.79 | 12.97 | 13.78 | 14.98 | 14.68 | 14.54 | 14.34 | 13.99 |
| 10 | 11.07 | 11.84 | 12.59 | 13.27 | 13.77 | 14.11 | 14.33 | 14.55 | 15.48 | 16.83 | 16.51 | 16.36 | 16.14 | 15.73 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.510 |
| SC2 | 0 | 8 | 11.387 |
| SC3 | -18 | 7 | 9.442 |
| SC4 | -25 | 6 | 7.659 |
| SC5 | -34 | 6 | 7.277 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.