ED-DP-345AC7-B24 C
17.20 kW
Defrost: None
Product code: ED-DP-245AE4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,349 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 97.4 m² |
| Inner volume | 21.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 135 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| ED-DP-245AE4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.96 | 7.92 | 7.92 | 7.95 | 7.94 | 7.90 | 7.82 | 7.98 | 8.49 | 9.21 | 9.00 | 8.94 | 8.85 | 8.72 |
| 5 | 10.02 | 10.05 | 10.12 | 10.21 | 10.22 | 10.17 | 10.07 | 10.19 | 10.81 | 11.71 | 11.37 | 11.25 | 11.07 | 10.80 |
| 6 | 12.03 | 12.18 | 12.34 | 12.51 | 12.57 | 12.53 | 12.42 | 12.51 | 13.25 | 14.33 | 13.87 | 13.68 | 13.42 | 12.98 |
| 7 | 14.02 | 14.30 | 14.59 | 14.82 | 14.95 | 14.95 | 14.83 | 14.90 | 15.77 | 17.04 | 16.47 | 16.24 | 15.88 | 15.30 |
| 8 | 15.85 | 16.32 | 16.76 | 17.15 | 17.36 | 17.39 | 17.28 | 17.36 | 18.36 | 19.81 | 19.17 | 18.88 | 18.45 | 17.72 |
| 9 | 17.50 | 18.15 | 18.76 | 19.31 | 19.64 | 19.78 | 19.76 | 19.82 | 20.96 | 22.61 | 21.89 | 21.56 | 21.05 | 20.19 |
| 10 | 19.03 | 19.90 | 20.70 | 21.32 | 21.76 | 21.98 | 22.01 | 22.17 | 23.47 | 25.36 | 24.63 | 24.28 | 23.71 | 22.71 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.630 |
| SC2 | 0 | 8 | 17.357 |
| SC3 | -18 | 7 | 14.890 |
| SC4 | -25 | 6 | 12.344 |
| SC5 | -34 | 6 | 12.073 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.