ED-DP-163AE4-B27 C
17.69 kW
Defrost: None
Product code: ED-DP-340AE4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,103 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 109.6 m² |
| Inner volume | 23.8 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 149 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | A |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| ED-DP-340AE4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.12 | 8.12 | 8.16 | 8.22 | 8.23 | 8.19 | 8.11 | 8.29 | 8.82 | 9.58 | 9.35 | 9.27 | 9.17 | 9.02 |
| 5 | 10.13 | 10.21 | 10.33 | 10.46 | 10.50 | 10.46 | 10.36 | 10.50 | 11.14 | 12.08 | 11.71 | 11.57 | 11.37 | 11.04 |
| 6 | 12.06 | 12.28 | 12.51 | 12.72 | 12.82 | 12.80 | 12.69 | 12.80 | 13.56 | 14.67 | 14.17 | 13.97 | 13.66 | 13.16 |
| 7 | 13.97 | 14.34 | 14.69 | 15.01 | 15.15 | 15.17 | 15.06 | 15.16 | 16.04 | 17.32 | 16.72 | 16.46 | 16.07 | 15.41 |
| 8 | 15.71 | 16.27 | 16.79 | 17.25 | 17.50 | 17.56 | 17.46 | 17.56 | 18.56 | 20.02 | 19.34 | 19.02 | 18.54 | 17.73 |
| 9 | 17.30 | 18.05 | 18.74 | 19.35 | 19.73 | 19.89 | 19.87 | 19.95 | 21.09 | 22.73 | 21.97 | 21.61 | 21.05 | 20.10 |
| 10 | 18.76 | 19.73 | 20.62 | 21.31 | 21.82 | 22.06 | 22.09 | 22.25 | 23.55 | 25.41 | 24.62 | 24.24 | 23.60 | 22.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.624 |
| SC2 | 0 | 8 | 17.555 |
| SC3 | -18 | 7 | 15.065 |
| SC4 | -25 | 6 | 12.506 |
| SC5 | -34 | 6 | 12.118 |
| A | 2148 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1835 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2148 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.