Skip to Content

Unit cooler ED-DP-163AG7-B27 C

Unit cooler ED-DP-163AG7-B27 C
Illustrative photo

Producer: Karyer · Line: ED-DP (Processing Room)

Product code: ED-DP-163AG7-B27 C

Cooling capacity i
18.29 kW
Air flow
8,237 m³/h
Fin spacing
7.0 mm
Air throw
11 m
Fans
1 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 8,237 m³/h
Air throw 11 m
External surface 108.2 m²
Inner volume 32.6 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 161 kg
Fans
Quantity 1
Diameter 630 mm
Speed 890 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 73.3 dB(A)
Energy class B
Connections
Inlet Ø28
Outlet Ø42
Defrost
ED-DP-163AG7-B27 C None

Performance

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
18.289 kW
Low speed (Y)
14.887 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 8.28 8.24 8.23 8.26 8.24 8.20 8.12 8.24 8.76 9.49 9.27 9.20 9.09 8.94
5 10.48 10.48 10.56 10.64 10.65 10.60 10.51 10.61 11.25 12.18 11.84 11.72 11.55 11.29
6 12.57 12.75 12.93 13.10 13.15 13.12 13.02 13.09 13.87 15.00 14.55 14.37 14.12 13.72
7 14.57 14.93 15.27 15.56 15.70 15.71 15.62 15.67 16.59 17.92 17.36 17.13 16.80 16.26
8 16.44 17.03 17.48 17.93 18.19 18.26 18.21 18.29 19.36 20.92 20.27 20.00 19.59 18.92
9 18.18 18.92 19.65 20.30 20.67 20.85 20.84 20.96 22.19 23.97 23.25 22.94 22.46 21.66
10 19.66 20.69 21.64 22.47 23.00 23.31 23.42 23.62 25.03 27.05 26.27 25.92 25.38 24.46

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 7.00 6.93 6.92 6.93 6.92 6.88 6.80 6.98 7.43 8.06 7.88 7.82 7.73 7.59
5 8.81 8.78 8.81 8.86 8.86 8.80 8.70 8.82 9.37 10.15 9.86 9.76 9.61 9.39
6 10.62 10.64 10.74 10.84 10.86 10.81 10.69 10.78 11.42 12.36 11.96 11.81 11.58 11.22
7 12.35 12.51 12.69 12.86 12.90 12.87 12.74 12.81 13.55 14.65 14.14 13.94 13.64 13.16
8 14.00 14.31 14.60 14.87 14.99 14.96 14.83 14.89 15.74 16.98 16.40 16.14 15.78 15.18
9 15.57 16.04 16.48 16.86 17.04 17.04 16.93 16.99 17.96 19.36 18.70 18.41 17.98 17.27
10 17.04 17.71 18.32 18.76 19.04 19.14 19.06 19.13 20.22 21.79 21.05 20.72 20.24 19.41

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 26.27221.052
SC2 0 8 18.28914.887
SC3 -18 7 15.63312.895
SC4 -25 6 12.93110.736
SC5 -34 6 12.62510.646

Dimensions

Dimension drawing of ED-DP-163AG7-B27 C
Dimension drawing
Dimensions as drawn
A 1568 mm
B 1700 mm
C 520 mm
F 1750 mm
G 660 mm
E1 1235 mm
D IN 1 x Ø28
D OUT 1 x Ø42
Overall [mm]
Length 1568 mm
Width 1700 mm
Height 660 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.