ED-DP-163AE7-B27 C
14.82 kW
Defrost: None
Product code: ED-DP-245AE7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,886 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 61.0 m² |
| Inner volume | 20.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 122 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | A |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-245AE7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.21 | 6.30 | 6.39 | 6.47 | 6.49 | 6.47 | 6.40 | 6.51 | 6.93 | 7.50 | 7.32 | 7.26 | 7.17 | 7.05 |
| 5 | 7.76 | 8.00 | 8.21 | 8.40 | 8.49 | 8.50 | 8.45 | 8.55 | 9.07 | 9.82 | 9.54 | 9.43 | 9.28 | 9.05 |
| 6 | 9.29 | 9.68 | 10.04 | 10.35 | 10.51 | 10.58 | 10.57 | 10.67 | 11.32 | 12.26 | 11.89 | 11.75 | 11.53 | 11.18 |
| 7 | 10.64 | 11.21 | 11.74 | 12.20 | 12.51 | 12.69 | 12.72 | 12.82 | 13.60 | 14.74 | 14.32 | 14.14 | 13.88 | 13.42 |
| 8 | 11.82 | 12.58 | 13.28 | 13.81 | 14.25 | 14.51 | 14.64 | 14.85 | 15.77 | 17.12 | 16.72 | 16.54 | 16.26 | 15.73 |
| 9 | 12.89 | 13.85 | 14.65 | 15.43 | 15.98 | 16.35 | 16.54 | 16.80 | 17.85 | 19.38 | 18.95 | 18.74 | 18.42 | 17.86 |
| 10 | 13.85 | 14.94 | 16.03 | 16.98 | 17.69 | 18.17 | 18.44 | 18.75 | 19.93 | 21.65 | 21.19 | 20.96 | 20.61 | 19.97 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.190 |
| SC2 | 0 | 8 | 14.847 |
| SC3 | -18 | 7 | 12.341 |
| SC4 | -25 | 6 | 10.041 |
| SC5 | -34 | 6 | 9.383 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.