ED-DP-335AE4-B22 C
12.42 kW
Defrost: None
Product code: ED-DP-340AC7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 7,495 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 45.8 m² |
| Inner volume | 15.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 129 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.3 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-340AC7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.27 | 5.22 | 5.19 | 5.18 | 5.15 | 5.10 | 5.04 | 5.10 | 5.41 | 5.85 | 5.70 | 5.65 | 5.57 | 5.45 |
| 5 | 6.80 | 6.81 | 6.84 | 6.89 | 6.88 | 6.83 | 6.76 | 6.81 | 7.21 | 7.79 | 7.57 | 7.49 | 7.38 | 7.22 |
| 6 | 8.32 | 8.40 | 8.53 | 8.65 | 8.69 | 8.67 | 8.61 | 8.65 | 9.16 | 9.89 | 9.59 | 9.48 | 9.31 | 9.06 |
| 7 | 9.75 | 10.00 | 10.23 | 10.44 | 10.54 | 10.57 | 10.53 | 10.58 | 11.20 | 12.11 | 11.74 | 11.60 | 11.38 | 11.02 |
| 8 | 11.07 | 11.45 | 11.82 | 12.16 | 12.39 | 12.50 | 12.50 | 12.56 | 13.31 | 14.41 | 13.98 | 13.80 | 13.53 | 13.10 |
| 9 | 12.23 | 12.77 | 13.27 | 13.72 | 13.98 | 14.18 | 14.28 | 14.43 | 15.32 | 16.63 | 16.25 | 16.05 | 15.75 | 15.23 |
| 10 | 13.32 | 14.03 | 14.61 | 15.18 | 15.59 | 15.86 | 16.00 | 16.20 | 17.20 | 18.67 | 18.25 | 18.06 | 17.76 | 17.25 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.252 |
| SC2 | 0 | 8 | 12.564 |
| SC3 | -18 | 7 | 10.497 |
| SC4 | -25 | 6 | 8.528 |
| SC5 | -34 | 6 | 8.357 |
| A | 2148 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1835 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2148 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.