ED-DP-440AC7-B22 C
16.68 kW
Defrost: None
Product code: ED-DP-435AE4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,612 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 108.8 m² |
| Inner volume | 21.0 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 160 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 945 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 66.0 dB(A) |
| Energy class | A |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| ED-DP-435AE4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.13 | 7.34 | 7.53 | 7.70 | 7.79 | 7.81 | 7.77 | 7.91 | 8.41 | 9.14 | 8.90 | 8.82 | 8.70 | 8.52 |
| 5 | 8.75 | 9.11 | 9.45 | 9.70 | 9.87 | 9.94 | 9.91 | 10.04 | 10.66 | 11.57 | 11.22 | 11.09 | 10.89 | 10.55 |
| 6 | 10.20 | 10.75 | 11.26 | 11.70 | 11.97 | 12.09 | 12.08 | 12.22 | 12.96 | 14.05 | 13.61 | 13.44 | 13.17 | 12.71 |
| 7 | 11.48 | 12.23 | 12.91 | 13.50 | 13.83 | 14.07 | 14.14 | 14.32 | 15.20 | 16.48 | 16.04 | 15.83 | 15.50 | 14.92 |
| 8 | 12.64 | 13.60 | 14.38 | 15.15 | 15.69 | 16.01 | 16.15 | 16.36 | 17.36 | 18.82 | 18.34 | 18.10 | 17.74 | 17.10 |
| 9 | ≈ 13.68 | 14.76 | 15.84 | 16.80 | 17.50 | 17.93 | 18.14 | 18.40 | 19.53 | 21.16 | 20.64 | 20.38 | 19.96 | 19.23 |
| 10 | 14.62 | 15.91 | 17.22 | 18.39 | 19.25 | 19.82 | 20.12 | 20.43 | 21.69 | 23.51 | 22.95 | 22.66 | 22.20 | 21.37 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.949 |
| SC2 | 0 | 8 | 16.361 |
| SC3 | -18 | 7 | 13.611 |
| SC4 | -25 | 6 | 11.259 |
| SC5 | -34 | 6 | 10.326 |
| A | 2748 mm |
|---|---|
| B | 900 mm |
| C | 325 mm |
| F | 940 mm |
| G | 410 mm |
| E1 | 2435 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2748 mm |
|---|---|
| Width | 900 mm |
| Height | 410 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.