ED-DP-440AE4-B22 C
23.27 kW
Defrost: None
Product code: ED-DP-445AC7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 15,225 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 80.8 m² |
| Inner volume | 26.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 195 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 760 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.2 dB(A) |
| Energy class | B |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| ED-DP-445AC7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.33 | 9.56 | 9.75 | 9.91 | 9.97 | 9.95 | 9.87 | 9.97 | 10.57 | 11.42 | 11.11 | 11.01 | 10.85 | 10.58 |
| 5 | 11.78 | 12.27 | 12.71 | 13.08 | 13.26 | 13.35 | 13.33 | 13.46 | 14.28 | 15.45 | 15.02 | 14.86 | 14.63 | 14.28 |
| 6 | 13.91 | 14.67 | 15.37 | 16.00 | 16.42 | 16.63 | 16.78 | 17.03 | 18.11 | 19.64 | 19.15 | 18.96 | 18.66 | 18.19 |
| 7 | 15.74 | 16.81 | 17.66 | 18.53 | 19.15 | 19.57 | 19.83 | 20.14 | 21.43 | 23.32 | 22.86 | 22.67 | 22.38 | 21.89 |
| 8 | 17.39 | 18.65 | 19.92 | 21.06 | 21.90 | 22.50 | 22.87 | 23.27 | 24.77 | 26.97 | 26.48 | 26.27 | 25.93 | 25.35 |
| 9 | ≈ 18.88 | 20.45 | 22.04 | 23.49 | 24.57 | 25.36 | 25.89 | 26.40 | 28.12 | 30.64 | 30.14 | 29.90 | 29.52 | 28.84 |
| 10 | ≈ 20.09 | 22.11 | 24.05 | 25.80 | 27.17 | 28.18 | 28.88 | 29.52 | 31.46 | 34.32 | 33.81 | 33.55 | 33.14 | 32.37 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.807 |
| SC2 | 0 | 8 | 23.271 |
| SC3 | -18 | 7 | 18.805 |
| SC4 | -25 | 6 | 15.374 |
| SC5 | -34 | 6 | 14.089 |
| A | 3548 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 570 mm |
| E1 | 3235 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 3548 mm |
|---|---|
| Width | 1050 mm |
| Height | 570 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.