ED-DP-263AE7-B27 C
30.90 kW
Defrost: None
Product code: ED-DP-445AE7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,769 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 122.1 m² |
| Inner volume | 42.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 221 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 760 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | A |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-DP-445AE7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.94 | 13.13 | 13.32 | 13.49 | 13.54 | 13.49 | 13.37 | 13.60 | 14.46 | 15.66 | 15.27 | 15.14 | 14.96 | 14.70 |
| 5 | 16.15 | 16.64 | 17.08 | 17.47 | 17.66 | 17.69 | 17.59 | 17.80 | 18.89 | 20.45 | 19.86 | 19.63 | 19.31 | 18.81 |
| 6 | 19.29 | 20.10 | 20.84 | 21.48 | 21.86 | 21.98 | 21.94 | 22.17 | 23.51 | 25.47 | 24.71 | 24.41 | 23.95 | 23.21 |
| 7 | 22.04 | 23.20 | 24.27 | 25.21 | 25.84 | 26.21 | 26.27 | 26.58 | 28.17 | 30.54 | 29.68 | 29.32 | 28.76 | 27.82 |
| 8 | 24.47 | 26.02 | 27.45 | 28.54 | 29.40 | 29.94 | 30.20 | 30.63 | 32.53 | 35.31 | 34.48 | 34.10 | 33.51 | 32.50 |
| 9 | 26.69 | 28.66 | 30.27 | 31.87 | 32.99 | 33.73 | 34.12 | 34.64 | 36.80 | 39.95 | 39.05 | 38.62 | 37.95 | 36.77 |
| 10 | 28.69 | 30.91 | 33.12 | 35.06 | 36.50 | 37.47 | 38.01 | 38.65 | 41.08 | 44.60 | 43.65 | 43.17 | 42.42 | 41.10 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 43.647 |
| SC2 | 0 | 8 | 30.627 |
| SC3 | -18 | 7 | 25.500 |
| SC4 | -25 | 6 | 20.841 |
| SC5 | -34 | 6 | 19.487 |
| A | 3548 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 570 mm |
| E1 | 3235 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3548 mm |
|---|---|
| Width | 1050 mm |
| Height | 570 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.