ED-140AE7-C21 C
6.13 kW
Defrost: None
Product code: ED-140AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 3,301 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 24.3 m² |
| Inner volume | 5.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 54 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-140AC4-C21 C | None |
|---|---|
| ED-140AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.60 | 2.55 | 2.53 | 2.52 | 2.50 | 2.47 | 2.45 | 2.48 | 2.63 | 2.85 | 2.78 | 2.76 | 2.73 | 2.68 |
| 5 | 3.38 | 3.36 | 3.35 | 3.35 | 3.33 | 3.30 | 3.26 | 3.28 | 3.48 | 3.76 | 3.66 | 3.62 | 3.58 | 3.51 |
| 6 | 4.19 | 4.19 | 4.22 | 4.25 | 4.24 | 4.21 | 4.16 | 4.17 | 4.41 | 4.76 | 4.62 | 4.56 | 4.49 | 4.38 |
| 7 | 4.96 | 5.04 | 5.12 | 5.18 | 5.19 | 5.17 | 5.12 | 5.13 | 5.42 | 5.85 | 5.66 | 5.59 | 5.48 | 5.32 |
| 8 | 5.66 | 5.81 | 5.95 | 6.09 | 6.17 | 6.18 | 6.14 | 6.14 | 6.49 | 7.01 | 6.78 | 6.69 | 6.56 | 6.35 |
| 9 | 6.28 | 6.50 | 6.71 | 6.89 | 6.99 | 7.05 | 7.06 | 7.11 | 7.54 | 8.17 | 7.94 | 7.83 | 7.68 | 7.43 |
| 10 | 6.86 | 7.17 | 7.42 | 7.66 | 7.82 | 7.91 | 7.94 | 8.00 | 8.48 | 9.19 | 8.96 | 8.87 | 8.72 | 8.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.963 |
| SC2 | 0 | 8 | 6.139 |
| SC3 | -18 | 7 | 5.194 |
| SC4 | -25 | 6 | 4.220 |
| SC5 | -34 | 6 | 4.201 |
| A | 948 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |