ED-335AC7-C21 C
11.16 kW
Defrost: Electric
Product code: ED-235AE4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,379 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 54.8 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 75 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-235AE4-C21 C | None |
|---|---|
| ED-235AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.80 | 4.83 | 4.87 | 4.92 | 4.92 | 4.89 | 4.84 | 4.94 | 5.26 | 5.71 | 5.58 | 5.53 | 5.48 | 5.40 |
| 5 | 6.02 | 6.15 | 6.26 | 6.37 | 6.40 | 6.39 | 6.33 | 6.41 | 6.80 | 7.36 | 7.14 | 7.07 | 6.96 | 6.79 |
| 6 | 7.22 | 7.46 | 7.67 | 7.85 | 7.92 | 7.94 | 7.88 | 7.95 | 8.42 | 9.11 | 8.82 | 8.70 | 8.53 | 8.26 |
| 7 | 8.29 | 8.65 | 8.98 | 9.26 | 9.44 | 9.52 | 9.48 | 9.55 | 10.09 | 10.92 | 10.57 | 10.42 | 10.20 | 9.83 |
| 8 | 9.23 | 9.73 | 10.18 | 10.52 | 10.77 | 10.89 | 10.92 | 11.04 | 11.71 | 12.68 | 12.33 | 12.18 | 11.92 | 11.47 |
| 9 | 10.10 | 10.75 | 11.26 | 11.77 | 12.10 | 12.29 | 12.35 | 12.49 | 13.24 | 14.34 | 13.95 | 13.77 | 13.50 | 13.02 |
| 10 | 10.89 | 11.63 | 12.35 | 12.99 | 13.41 | 13.68 | 13.78 | 13.95 | 14.79 | 16.01 | 15.59 | 15.39 | 15.07 | 14.53 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.591 |
| SC2 | 0 | 8 | 11.040 |
| SC3 | -18 | 7 | 9.344 |
| SC4 | -25 | 6 | 7.671 |
| SC5 | -34 | 6 | 7.283 |
| A | 1548 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.