ED-235AC4-C21 C
9.59 kW
Defrost: None
Product code: ED-235AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,761 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 34.3 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 72 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-235AE7-C21 C | None |
|---|---|
| ED-235AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.03 | 4.00 | 3.99 | 3.98 | 3.96 | 3.91 | 3.86 | 3.92 | 4.16 | 4.50 | 4.38 | 4.34 | 4.29 | 4.19 |
| 5 | 5.17 | 5.20 | 5.24 | 5.28 | 5.27 | 5.23 | 5.16 | 5.21 | 5.52 | 5.97 | 5.78 | 5.72 | 5.63 | 5.51 |
| 6 | 6.31 | 6.39 | 6.50 | 6.60 | 6.64 | 6.62 | 6.55 | 6.59 | 6.98 | 7.53 | 7.28 | 7.19 | 7.05 | 6.84 |
| 7 | 7.36 | 7.58 | 7.78 | 7.95 | 8.04 | 8.04 | 7.99 | 8.03 | 8.50 | 9.18 | 8.87 | 8.75 | 8.57 | 8.28 |
| 8 | 8.32 | 8.65 | 8.95 | 9.23 | 9.40 | 9.48 | 9.46 | 9.51 | 10.07 | 10.88 | 10.52 | 10.38 | 10.16 | 9.79 |
| 9 | 9.17 | 9.62 | 10.03 | 10.40 | 10.59 | 10.73 | 10.78 | 10.89 | 11.55 | 12.52 | 12.19 | 12.04 | 11.78 | 11.36 |
| 10 | 9.97 | 10.55 | 11.02 | 11.48 | 11.80 | 11.99 | 12.07 | 12.21 | 12.95 | 14.03 | 13.69 | 13.52 | 13.28 | 12.85 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.686 |
| SC2 | 0 | 8 | 9.508 |
| SC3 | -18 | 7 | 7.996 |
| SC4 | -25 | 6 | 6.504 |
| SC5 | -34 | 6 | 6.337 |
| A | 1548 mm |
|---|---|
| B | 1030 mm |
| C | 285 mm |
| F | 985 mm |
| G | 367 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 1030 mm |
| Height | 367 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.