ED-330AE4-C25 C
8.89 kW
Defrost: None
Product code: ED-430AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 5,618 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 31.5 m² |
| Inner volume | 9.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 91 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.4 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-430AC7-C21 C | None |
|---|---|
| ED-430AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.81 | 3.74 | 3.69 | 3.66 | 3.62 | 3.57 | 3.52 | 3.54 | 3.75 | 4.04 | 3.93 | 3.89 | 3.83 | 3.74 |
| 5 | 4.99 | 4.95 | 4.93 | 4.93 | 4.89 | 4.84 | 4.77 | 4.78 | 5.05 | 5.45 | 5.28 | 5.22 | 5.14 | 5.02 |
| 6 | 6.16 | 6.18 | 6.22 | 6.26 | 6.25 | 6.21 | 6.14 | 6.14 | 6.49 | 7.00 | 6.76 | 6.68 | 6.56 | 6.38 |
| 7 | 7.31 | 7.42 | 7.53 | 7.63 | 7.66 | 7.64 | 7.58 | 7.59 | 8.02 | 8.65 | 8.36 | 8.25 | 8.09 | 7.83 |
| 8 | 8.36 | 8.56 | 8.77 | 8.97 | 9.09 | 9.11 | 9.07 | 9.09 | 9.61 | 10.38 | 10.05 | 9.92 | 9.72 | 9.40 |
| 9 | 9.29 | 9.59 | 9.89 | 10.16 | 10.33 | 10.42 | 10.46 | 10.55 | 11.19 | 12.13 | 11.78 | 11.63 | 11.40 | 11.02 |
| 10 | 10.16 | 10.58 | 10.94 | 11.29 | 11.53 | 11.69 | 11.76 | 11.87 | 12.59 | 13.65 | 13.33 | 13.19 | 12.98 | 12.61 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.330 |
| SC2 | 0 | 8 | 9.086 |
| SC3 | -18 | 7 | 7.641 |
| SC4 | -25 | 6 | 6.219 |
| SC5 | -34 | 6 | 6.170 |
| A | 2348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2035 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.