ED-330AC4-C21 C
8.78 kW
Defrost: None
Product code: ED-330AE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 3,059 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 57.1 m² |
| Inner volume | 12.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 79 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-330AE4-C25 C | None |
|---|---|
| ED-330AE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.10 | 4.11 | 4.14 | 4.18 | 4.19 | 4.17 | 4.13 | 4.22 | 4.50 | 4.88 | 4.76 | 4.72 | 4.67 | 4.59 |
| 5 | 5.10 | 5.16 | 5.23 | 5.31 | 5.33 | 5.32 | 5.26 | 5.34 | 5.66 | 6.14 | 5.95 | 5.88 | 5.77 | 5.61 |
| 6 | 6.05 | 6.19 | 6.32 | 6.44 | 6.50 | 6.49 | 6.44 | 6.50 | 6.88 | 7.45 | 7.19 | 7.09 | 6.94 | 6.68 |
| 7 | 7.00 | 7.21 | 7.41 | 7.59 | 7.67 | 7.69 | 7.63 | 7.68 | 8.13 | 8.78 | 8.48 | 8.35 | 8.16 | 7.83 |
| 8 | 7.85 | 8.17 | 8.46 | 8.70 | 8.85 | 8.88 | 8.83 | 8.89 | 9.39 | 10.14 | 9.80 | 9.64 | 9.41 | 9.02 |
| 9 | 8.63 | 9.04 | 9.42 | 9.75 | 9.96 | 10.04 | 10.02 | 10.08 | 10.67 | 11.50 | 11.12 | 10.95 | 10.67 | 10.23 |
| 10 | 9.34 | 9.87 | 10.36 | 10.73 | 11.00 | 11.13 | 11.15 | 11.23 | 11.89 | 12.84 | 12.45 | 12.26 | 11.96 | 11.45 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.453 |
| SC2 | 0 | 8 | 8.885 |
| SC3 | -18 | 7 | 7.619 |
| SC4 | -25 | 6 | 6.320 |
| SC5 | -34 | 6 | 6.088 |
| A | 1848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 1535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.