ED-263AE7-C27 C
30.90 kW
Defrost: None
Product code: ED-250AE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,287 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 137.0 m² |
| Inner volume | 30.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 160 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-250AE4-C21 C | None |
|---|---|
| ED-250AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.39 | 13.26 | 13.21 | 13.21 | 13.14 | 13.02 | 12.88 | 13.07 | 13.89 | 15.04 | 14.70 | 14.58 | 14.42 | 14.19 |
| 5 | 17.16 | 17.20 | 17.29 | 17.38 | 17.34 | 17.21 | 17.01 | 17.16 | 18.19 | 19.66 | 19.09 | 18.90 | 18.63 | 18.25 |
| 6 | 20.93 | 21.22 | 21.50 | 21.71 | 21.78 | 21.68 | 21.46 | 21.56 | 22.82 | 24.64 | 23.85 | 23.56 | 23.13 | 22.48 |
| 7 | 24.42 | 25.03 | 25.62 | 26.14 | 26.35 | 26.33 | 26.12 | 26.19 | 27.71 | 29.93 | 28.94 | 28.55 | 27.98 | 27.06 |
| 8 | 27.45 | 28.39 | 29.26 | 30.04 | 30.50 | 30.64 | 30.65 | 30.89 | 32.74 | 35.35 | 34.22 | 33.75 | 33.05 | 31.89 |
| 9 | 30.30 | 31.62 | 32.68 | 33.73 | 34.39 | 34.72 | 34.81 | 35.08 | 37.18 | 40.25 | 39.19 | 38.72 | 38.01 | 36.83 |
| 10 | 32.95 | 34.53 | 36.08 | 37.45 | 38.31 | 38.81 | 38.98 | 39.31 | 41.67 | 45.10 | 43.93 | 43.40 | 42.60 | 41.23 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 43.933 |
| SC2 | 0 | 8 | 30.885 |
| SC3 | -18 | 7 | 26.252 |
| SC4 | -25 | 6 | 21.497 |
| SC5 | -34 | 6 | 21.022 |
| A | 2368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 2035 mm |
| E2 | 1018 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.