ED-263AE7-C27 C
30.90 kW
Defrost: Electric
Product code: ED-250AE4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 13,287 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 137.0 m² |
| Inner volume | 30.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 160 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-250AE4-C21 C | None |
|---|---|
| ED-250AE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.05 | 11.94 | 11.92 | 11.95 | 11.93 | 11.87 | 11.79 | 12.04 | 12.82 | 13.92 | 13.66 | 13.59 | 13.44 | 13.24 |
| 5 | 15.81 | 15.84 | 15.92 | 16.03 | 16.03 | 15.95 | 15.81 | 16.02 | 17.01 | 18.43 | 17.97 | 17.82 | 17.61 | 17.32 |
| 6 | 19.62 | 19.85 | 20.05 | 20.31 | 20.39 | 20.34 | 20.17 | 20.33 | 21.55 | 23.31 | 22.62 | 22.38 | 22.02 | 21.48 |
| 7 | 23.19 | 23.74 | 24.26 | 24.72 | 24.93 | 24.92 | 24.77 | 24.90 | 26.36 | 28.51 | 27.62 | 27.28 | 26.77 | 25.97 |
| 8 | 26.37 | 27.22 | 28.04 | 28.79 | 29.25 | 29.48 | 29.50 | 29.61 | 31.34 | 33.89 | 32.85 | 32.42 | 31.79 | 30.75 |
| 9 | 29.28 | 30.50 | 31.62 | 32.50 | 33.15 | 33.49 | 33.60 | 33.90 | 35.96 | 38.96 | 37.98 | 37.54 | 36.90 | 35.69 |
| 10 | 32.00 | 33.47 | 34.93 | 36.23 | 37.07 | 37.57 | 37.76 | 38.12 | 40.43 | 43.79 | 42.70 | 42.21 | 41.46 | 40.18 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 42.701 |
| SC2 | 0 | 8 | 29.611 |
| SC3 | -18 | 7 | 24.831 |
| SC4 | -25 | 6 | 20.054 |
| SC5 | -34 | 6 | 19.692 |
| A | 2368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 2035 mm |
| E2 | 1018 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.