ED-445AE7-C23 C
36.05 kW
Defrost: None
Product code: ED-263AG7-C27 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 16,477 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 216.3 m² |
| Inner volume | 64.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 278 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 1,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.3 dB(A) |
| Energy class | B |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| ED-263AG7-C27 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 14.94 | 14.82 | 14.82 | 14.89 | 14.89 | 14.85 | 14.76 | 15.06 | 16.03 | 17.41 | 17.09 | 16.98 | 16.83 | 16.61 |
| 5 | 19.29 | 19.30 | 19.40 | 19.55 | 19.59 | 19.53 | 19.39 | 19.66 | 20.88 | 22.63 | 22.09 | 21.90 | 21.63 | 21.23 |
| 6 | 23.66 | 23.86 | 24.13 | 24.38 | 24.49 | 24.45 | 24.29 | 24.51 | 25.99 | 28.14 | 27.36 | 27.07 | 26.64 | 25.98 |
| 7 | 27.79 | 28.31 | 28.83 | 29.32 | 29.54 | 29.56 | 29.38 | 29.56 | 31.32 | 33.89 | 32.88 | 32.49 | 31.90 | 30.94 |
| 8 | 31.72 | 32.62 | 33.46 | 34.22 | 34.53 | 34.67 | 34.54 | 34.73 | 36.78 | 39.78 | 38.58 | 38.09 | 37.36 | 36.15 |
| 9 | 35.40 | 36.60 | 37.82 | 38.90 | 39.55 | 39.81 | 39.78 | 40.01 | 42.37 | 45.80 | 44.47 | 43.89 | 43.01 | 41.54 |
| 10 | 38.61 | 40.35 | 41.96 | 43.41 | 44.33 | 44.87 | 45.03 | 45.34 | 48.02 | 51.91 | 50.44 | 49.78 | 48.77 | 47.06 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.64 | 12.51 | 12.49 | 12.55 | 12.56 | 12.52 | 12.44 | 12.84 | 13.68 | 14.82 | 14.56 | 14.48 | 14.36 | 14.20 |
| 5 | 16.26 | 16.18 | 16.22 | 16.32 | 16.34 | 16.28 | 16.13 | 16.43 | 17.47 | 19.04 | 18.50 | 18.34 | 18.11 | 17.77 |
| 6 | 19.86 | 19.91 | 20.05 | 20.23 | 20.28 | 20.21 | 20.02 | 20.26 | 21.49 | 23.28 | 22.60 | 22.35 | 21.97 | 21.37 |
| 7 | 23.48 | 23.67 | 23.94 | 24.21 | 24.32 | 24.27 | 24.05 | 24.23 | 25.67 | 27.78 | 26.88 | 26.52 | 25.98 | 25.15 |
| 8 | 26.89 | 27.33 | 27.79 | 28.25 | 28.45 | 28.41 | 28.17 | 28.33 | 29.97 | 32.38 | 31.31 | 30.85 | 30.19 | 29.10 |
| 9 | 30.16 | 30.89 | 31.60 | 32.25 | 32.58 | 32.60 | 32.38 | 32.49 | 34.35 | 37.07 | 35.84 | 35.30 | 34.51 | 33.20 |
| 10 | 33.24 | 34.32 | 35.47 | 36.10 | 36.58 | 36.73 | 36.56 | 36.73 | 38.83 | 41.87 | 40.48 | 39.87 | 38.97 | 37.42 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 50.441 | 40.482 |
| SC2 | 0 | 8 | 34.733 | 28.328 |
| SC3 | -18 | 7 | 29.435 | 24.273 |
| SC4 | -25 | 6 | 24.129 | 20.045 |
| SC5 | -34 | 6 | 23.729 | 19.893 |
| A | 2768 mm |
|---|---|
| B | 1720 mm |
| C | 455 mm |
| F | 1645 mm |
| G | 483 mm |
| E1 | 2435 mm |
| E2 | 1218 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2768 mm |
|---|---|
| Width | 1720 mm |
| Height | 483 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.