ED-145AC7-C23 C
6.70 kW
Defrost: None
Product code: ED-330AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 4,213 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 23.8 m² |
| Inner volume | 8.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 73 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.4 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-330AC7-C21 C | None |
|---|---|
| ED-330AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.74 | 2.72 | 2.71 | 2.71 | 2.69 | 2.67 | 2.63 | 2.65 | 2.81 | 3.04 | 2.96 | 2.93 | 2.88 | 2.82 |
| 5 | 3.53 | 3.55 | 3.58 | 3.61 | 3.61 | 3.59 | 3.55 | 3.57 | 3.78 | 4.08 | 3.96 | 3.92 | 3.86 | 3.78 |
| 6 | 4.32 | 4.40 | 4.47 | 4.54 | 4.57 | 4.57 | 4.54 | 4.56 | 4.83 | 5.21 | 5.06 | 5.00 | 4.91 | 4.78 |
| 7 | 5.05 | 5.21 | 5.36 | 5.49 | 5.56 | 5.58 | 5.57 | 5.60 | 5.93 | 6.41 | 6.22 | 6.15 | 6.04 | 5.86 |
| 8 | 5.70 | 5.93 | 6.15 | 6.35 | 6.49 | 6.57 | 6.60 | 6.65 | 7.05 | 7.63 | 7.42 | 7.34 | 7.21 | 6.99 |
| 9 | 6.29 | 6.61 | 6.90 | 7.14 | 7.32 | 7.44 | 7.51 | 7.59 | 8.07 | 8.76 | 8.57 | 8.49 | 8.36 | 8.15 |
| 10 | 6.83 | 7.24 | 7.58 | 7.91 | 8.16 | 8.32 | 8.41 | 8.52 | 9.06 | 9.84 | 9.64 | 9.54 | 9.40 | 9.16 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.635 |
| SC2 | 0 | 8 | 6.652 |
| SC3 | -18 | 7 | 5.521 |
| SC4 | -25 | 6 | 4.465 |
| SC5 | -34 | 6 | 4.341 |
| A | 1848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 1535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.