ED-140AE4-C21 C
7.35 kW
Defrost: None
Product code: ED-330AE7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 3,370 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 35.8 m² |
| Inner volume | 12.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 76 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-330AE7-C25 C | None |
|---|---|
| ED-330AE7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.41 | 3.37 | 3.36 | 3.36 | 3.35 | 3.32 | 3.28 | 3.34 | 3.55 | 3.85 | 3.76 | 3.73 | 3.70 | 3.64 |
| 5 | 4.34 | 4.34 | 4.35 | 4.38 | 4.37 | 4.35 | 4.30 | 4.34 | 4.61 | 4.99 | 4.84 | 4.79 | 4.72 | 4.61 |
| 6 | 5.26 | 5.31 | 5.36 | 5.42 | 5.44 | 5.42 | 5.36 | 5.40 | 5.72 | 6.19 | 5.98 | 5.91 | 5.79 | 5.61 |
| 7 | 6.18 | 6.26 | 6.37 | 6.48 | 6.53 | 6.52 | 6.47 | 6.50 | 6.88 | 7.44 | 7.18 | 7.08 | 6.92 | 6.67 |
| 8 | 7.03 | 7.21 | 7.38 | 7.54 | 7.62 | 7.63 | 7.59 | 7.63 | 8.07 | 8.71 | 8.43 | 8.30 | 8.11 | 7.79 |
| 9 | 7.83 | 8.10 | 8.36 | 8.58 | 8.71 | 8.76 | 8.73 | 8.78 | 9.29 | 10.02 | 9.70 | 9.55 | 9.33 | 8.95 |
| 10 | 8.55 | 8.91 | 9.25 | 9.55 | 9.75 | 9.85 | 9.87 | 9.94 | 10.50 | 11.33 | 10.98 | 10.82 | 10.56 | 10.13 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.981 |
| SC2 | 0 | 8 | 7.633 |
| SC3 | -18 | 7 | 6.503 |
| SC4 | -25 | 6 | 5.362 |
| SC5 | -34 | 6 | 5.277 |
| A | 1848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 1535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.