ED-330AE7-C21 C
8.37 kW
Defrost: None
Product code: ED-330AC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,506 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 38.0 m² |
| Inner volume | 8.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-330AC4-C25 C | None |
|---|---|
| ED-330AC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.47 | 3.51 | 3.56 | 3.60 | 3.62 | 3.61 | 3.58 | 3.65 | 3.88 | 4.20 | 4.11 | 4.08 | 4.03 | 3.97 |
| 5 | 4.36 | 4.48 | 4.57 | 4.66 | 4.71 | 4.71 | 4.69 | 4.75 | 5.04 | 5.46 | 5.30 | 5.25 | 5.17 | 5.05 |
| 6 | 5.18 | 5.39 | 5.58 | 5.74 | 5.83 | 5.87 | 5.84 | 5.90 | 6.26 | 6.78 | 6.58 | 6.50 | 6.38 | 6.19 |
| 7 | 5.90 | 6.20 | 6.47 | 6.71 | 6.83 | 6.93 | 6.95 | 7.04 | 7.48 | 8.12 | 7.90 | 7.80 | 7.65 | 7.40 |
| 8 | 6.56 | 6.96 | 7.28 | 7.60 | 7.81 | 7.94 | 8.00 | 8.10 | 8.60 | 9.33 | 9.10 | 9.00 | 8.85 | 8.57 |
| 9 | 7.16 | 7.62 | 8.08 | 8.49 | 8.77 | 8.95 | 9.04 | 9.16 | 9.73 | 10.55 | 10.31 | 10.19 | 10.01 | 9.68 |
| 10 | 7.60 | 8.28 | 8.85 | 9.36 | 9.72 | 9.95 | 10.08 | 10.23 | 10.87 | 11.79 | 11.52 | 11.39 | 11.18 | 10.80 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.520 |
| SC2 | 0 | 8 | 8.099 |
| SC3 | -18 | 7 | 6.778 |
| SC4 | -25 | 6 | 5.581 |
| SC5 | -34 | 6 | 5.234 |
| A | 1848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 1535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.