ED-345AC4-C23 C
26.59 kW
Defrost: None
Product code: ED-345AE7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 13,632 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 91.6 m² |
| Inner volume | 32.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 159 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 1,050 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | B |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-345AE7-C23 C | None |
|---|---|
| ED-345AE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.15 | 11.04 | 10.98 | 10.96 | 10.88 | 10.76 | 10.61 | 10.70 | 11.34 | 12.24 | 11.92 | 11.80 | 11.63 | 11.36 |
| 5 | 14.35 | 14.41 | 14.49 | 14.57 | 14.55 | 14.44 | 14.27 | 14.33 | 15.18 | 16.38 | 15.87 | 15.70 | 15.45 | 15.09 |
| 6 | 17.55 | 17.82 | 18.04 | 18.30 | 18.39 | 18.34 | 18.19 | 18.24 | 19.30 | 20.83 | 20.16 | 19.91 | 19.55 | 18.99 |
| 7 | 20.50 | 21.07 | 21.60 | 22.07 | 22.31 | 22.34 | 22.25 | 22.32 | 23.63 | 25.53 | 24.72 | 24.41 | 23.94 | 23.19 |
| 8 | 23.14 | 23.99 | 24.80 | 25.53 | 26.01 | 26.27 | 26.33 | 26.47 | 28.02 | 30.31 | 29.43 | 29.06 | 28.51 | 27.57 |
| 9 | 25.53 | 26.72 | 27.81 | 28.68 | 29.32 | 29.73 | 29.93 | 30.22 | 32.07 | 34.78 | 33.97 | 33.62 | 33.07 | 32.06 |
| 10 | 27.76 | 29.31 | 30.58 | 31.81 | 32.68 | 33.24 | 33.53 | 33.90 | 35.99 | 39.04 | 38.17 | 37.77 | 37.16 | 36.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 38.166 |
| SC2 | 0 | 8 | 26.472 |
| SC3 | -18 | 7 | 22.192 |
| SC4 | -25 | 6 | 18.036 |
| SC5 | -34 | 6 | 17.626 |
| A | 2748 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 441 mm |
| E1 | 2435 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2748 mm |
|---|---|
| Width | 1210 mm |
| Height | 441 mm |
Our engineers answer with a selection for your conditions.