ED-345AC4-C23 C
26.59 kW
Defrost: None
Product code: ED-250AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,156 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 85.8 m² |
| Inner volume | 30.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 153 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.6 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-250AE7-C21 C | None |
|---|---|
| ED-250AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.49 | 11.26 | 11.12 | 11.04 | 10.92 | 10.77 | 10.61 | 10.68 | 11.31 | 12.21 | 11.88 | 11.75 | 11.57 | 11.30 |
| 5 | 14.97 | 14.86 | 14.81 | 14.79 | 14.69 | 14.53 | 14.32 | 14.35 | 15.18 | 16.37 | 15.86 | 15.68 | 15.44 | 15.07 |
| 6 | 18.41 | 18.48 | 18.60 | 18.72 | 18.69 | 18.56 | 18.34 | 18.35 | 19.40 | 20.90 | 20.21 | 19.95 | 19.59 | 19.03 |
| 7 | 21.81 | 22.13 | 22.44 | 22.74 | 22.81 | 22.76 | 22.57 | 22.57 | 23.86 | 25.74 | 24.88 | 24.54 | 24.05 | 23.25 |
| 8 | 24.90 | 25.50 | 26.11 | 26.70 | 26.99 | 27.05 | 26.90 | 26.94 | 28.50 | 30.76 | 29.79 | 29.38 | 28.77 | 27.78 |
| 9 | 27.64 | 28.54 | 29.41 | 30.20 | 30.70 | 30.92 | 31.03 | 31.25 | 33.15 | 35.86 | 34.78 | 34.31 | 33.61 | 32.44 |
| 10 | 30.22 | 31.47 | 32.50 | 33.56 | 34.23 | 34.65 | 34.84 | 35.13 | 37.26 | 40.37 | 39.39 | 38.95 | 38.27 | 37.14 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 39.392 |
| SC2 | 0 | 8 | 26.941 |
| SC3 | -18 | 7 | 22.769 |
| SC4 | -25 | 6 | 18.597 |
| SC5 | -34 | 6 | 18.447 |
| A | 2368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 2035 mm |
| E2 | 1018 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.