ED-345AC4-C23 C
26.59 kW
Defrost: None
Product code: ED-250AE7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 14,156 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 85.8 m² |
| Inner volume | 30.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 153 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.6 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-250AE7-C21 C | None |
|---|---|
| ED-250AE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.26 | 10.07 | 9.96 | 9.92 | 9.84 | 9.75 | 9.65 | 9.76 | 10.36 | 11.19 | 10.92 | 10.83 | 10.69 | 10.49 |
| 5 | 13.72 | 13.61 | 13.57 | 13.57 | 13.50 | 13.39 | 13.24 | 13.32 | 14.11 | 15.24 | 14.83 | 14.69 | 14.49 | 14.21 |
| 6 | 17.18 | 17.22 | 17.33 | 17.45 | 17.44 | 17.34 | 17.17 | 17.23 | 18.23 | 19.68 | 19.08 | 18.87 | 18.56 | 18.10 |
| 7 | 20.62 | 20.88 | 21.17 | 21.41 | 21.52 | 21.49 | 21.34 | 21.39 | 22.63 | 24.44 | 23.67 | 23.37 | 22.95 | 22.25 |
| 8 | 23.83 | 24.39 | 24.93 | 25.43 | 25.69 | 25.76 | 25.65 | 25.72 | 27.22 | 29.41 | 28.52 | 28.15 | 27.60 | 26.70 |
| 9 | 26.65 | 27.48 | 28.30 | 29.06 | 29.57 | 29.85 | 29.97 | 30.11 | 31.89 | 34.47 | 33.48 | 33.05 | 32.40 | 31.32 |
| 10 | 29.29 | 30.44 | 31.53 | 32.43 | 33.09 | 33.52 | 33.72 | 34.03 | 36.12 | 39.17 | 38.26 | 37.84 | 37.21 | 36.07 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 38.257 |
| SC2 | 0 | 8 | 25.715 |
| SC3 | -18 | 7 | 21.476 |
| SC4 | -25 | 6 | 17.326 |
| SC5 | -34 | 6 | 17.208 |
| A | 2368 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 2035 mm |
| E2 | 1018 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 2368 mm |
|---|---|
| Width | 1210 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.