ED-250AE7-C21 C
26.94 kW
Defrost: None
Product code: ED-445AC7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 19,580 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 81.4 m² |
| Inner volume | 29.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 181 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 1,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-445AC7-C23 C | None |
|---|---|
| ED-445AC7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.61 | 11.43 | 11.31 | 11.23 | 11.10 | 10.94 | 10.77 | 10.79 | 11.40 | 12.27 | 11.90 | 11.76 | 11.56 | 11.27 |
| 5 | 15.18 | 15.17 | 15.19 | 15.23 | 15.15 | 15.00 | 14.79 | 14.79 | 15.63 | 16.84 | 16.30 | 16.11 | 15.85 | 15.45 |
| 6 | 18.74 | 18.98 | 19.21 | 19.39 | 19.45 | 19.37 | 19.19 | 19.18 | 20.28 | 21.86 | 21.14 | 20.88 | 20.50 | 19.93 |
| 7 | 22.00 | 22.54 | 23.09 | 23.62 | 23.87 | 23.91 | 23.79 | 23.83 | 25.21 | 27.22 | 26.37 | 26.04 | 25.56 | 24.80 |
| 8 | 24.82 | 25.67 | 26.48 | 27.23 | 27.65 | 27.95 | 28.10 | 28.33 | 30.07 | 32.62 | 31.80 | 31.43 | 30.87 | 29.97 |
| 9 | 27.47 | 28.68 | 29.67 | 30.68 | 31.38 | 31.83 | 32.07 | 32.37 | 34.37 | 37.30 | 36.48 | 36.14 | 35.63 | 34.77 |
| 10 | 29.93 | 31.39 | 32.85 | 34.16 | 35.06 | 35.68 | 36.04 | 36.44 | 38.70 | 42.02 | 41.15 | 40.77 | 40.20 | 39.22 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 41.149 |
| SC2 | 0 | 8 | 28.330 |
| SC3 | -18 | 7 | 23.752 |
| SC4 | -25 | 6 | 19.214 |
| SC5 | -34 | 6 | 18.818 |
| A | 3548 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 441 mm |
| E1 | 3235 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3548 mm |
|---|---|
| Width | 1210 mm |
| Height | 441 mm |
Our engineers answer with a selection for your conditions.