ED-335AC7-C21 C
11.16 kW
Defrost: Electric
Product code: ED-530AC7-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,021 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 39.3 m² |
| Inner volume | 12.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 110 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.4 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-530AC7-C21 C | None |
|---|---|
| ED-530AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.65 | 4.63 | 4.63 | 4.63 | 4.60 | 4.55 | 4.49 | 4.52 | 4.79 | 5.17 | 5.02 | 4.97 | 4.89 | 4.77 |
| 5 | 5.97 | 6.05 | 6.12 | 6.19 | 6.20 | 6.17 | 6.10 | 6.13 | 6.49 | 7.00 | 6.78 | 6.71 | 6.60 | 6.44 |
| 6 | 7.28 | 7.47 | 7.64 | 7.80 | 7.86 | 7.87 | 7.83 | 7.86 | 8.32 | 8.98 | 8.71 | 8.60 | 8.44 | 8.20 |
| 7 | 8.43 | 8.75 | 9.04 | 9.31 | 9.49 | 9.60 | 9.61 | 9.64 | 10.21 | 11.05 | 10.73 | 10.60 | 10.41 | 10.10 |
| 8 | 9.45 | 9.90 | 10.32 | 10.64 | 10.90 | 11.06 | 11.15 | 11.27 | 11.97 | 13.00 | 12.70 | 12.58 | 12.39 | 12.07 |
| 9 | 10.39 | 10.92 | 11.48 | 11.97 | 12.32 | 12.55 | 12.68 | 12.83 | 13.63 | 14.81 | 14.49 | 14.35 | 14.13 | 13.77 |
| 10 | 11.25 | 11.95 | 12.65 | 13.26 | 13.71 | 14.02 | 14.20 | 14.41 | 15.31 | 16.63 | 16.29 | 16.14 | 15.90 | 15.48 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.294 |
| SC2 | 0 | 8 | 11.270 |
| SC3 | -18 | 7 | 9.393 |
| SC4 | -25 | 6 | 7.644 |
| SC5 | -34 | 6 | 7.328 |
| A | 2848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 2535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.