ED-630AE7-C21 C
17.29 kW
Defrost: None
Product code: ED-630AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,913 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 75.6 m² |
| Inner volume | 14.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 133 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.1 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-630AC4-C21 C | None |
|---|---|
| ED-630AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.94 | 7.26 | 7.54 | 7.77 | 7.87 | 7.92 | 7.90 | 8.03 | 8.54 | 9.26 | 9.04 | 8.96 | 8.86 | 8.70 |
| 5 | 8.44 | 8.96 | 9.42 | 9.83 | 10.04 | 10.21 | 10.29 | 10.47 | 11.14 | 12.12 | 11.85 | 11.73 | 11.56 | 11.28 |
| 6 | 9.72 | 10.46 | 11.03 | 11.62 | 12.03 | 12.30 | 12.44 | 12.66 | 13.47 | 14.66 | 14.35 | 14.22 | 14.03 | 13.70 |
| 7 | ≈ 10.86 | 11.73 | 12.61 | 13.40 | 13.98 | 14.37 | 14.60 | 14.87 | 15.83 | 17.23 | 16.88 | 16.72 | 16.49 | 16.08 |
| 8 | 11.30 | 12.96 | 14.08 | 15.10 | 15.87 | 16.40 | 16.74 | 17.08 | 18.19 | 19.81 | 19.43 | 19.26 | 18.99 | 18.50 |
| 9 | ≈ 12.59 | 14.09 | 15.46 | 16.71 | 17.68 | 18.39 | 18.85 | 19.29 | 20.55 | 22.39 | 22.01 | 21.82 | 21.51 | 20.96 |
| 10 | ≈ 5.46 | ≈ 15.11 | 16.73 | 18.23 | 19.42 | 20.32 | 20.92 | 21.47 | 22.90 | 24.97 | 24.59 | 24.39 | 24.06 | 23.44 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.593 |
| SC2 | 0 | 8 | 17.083 |
| SC3 | -18 | 7 | 13.655 |
| SC4 | -25 | 6 | 11.032 |
| SC5 | -34 | 6 | 9.887 |
| A | 3348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 3035 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 3348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.