ED-630AE7-C21 C
17.29 kW
Defrost: Electric
Product code: ED-630AC4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 7,913 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 75.6 m² |
| Inner volume | 14.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 133 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.1 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-630AC4-C21 C | None |
|---|---|
| ED-630AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.36 | 6.62 | 6.83 | 7.04 | 7.17 | 7.22 | 7.22 | 7.38 | 7.86 | 8.54 | 8.38 | 8.32 | 8.24 | 8.13 |
| 5 | 7.95 | 8.42 | 8.84 | 9.22 | 9.47 | 9.63 | 9.67 | 9.84 | 10.48 | 11.39 | 11.13 | 11.04 | 10.90 | 10.67 |
| 6 | 9.28 | 9.96 | 10.49 | 11.04 | 11.43 | 11.69 | 11.83 | 12.07 | 12.85 | 14.00 | 13.73 | 13.62 | 13.45 | 13.16 |
| 7 | 10.47 | 11.27 | 12.10 | 12.84 | 13.39 | 13.76 | 13.99 | 14.27 | 15.19 | 16.56 | 16.24 | 16.10 | 15.89 | 15.53 |
| 8 | ≈ 11.12 | 12.55 | 13.60 | 14.56 | 15.29 | 15.80 | 16.13 | 16.48 | 17.55 | 19.13 | 18.78 | 18.63 | 18.38 | 17.94 |
| 9 | ≈ 12.36 | 13.71 | 15.01 | 16.20 | 17.12 | 17.80 | 18.24 | 18.68 | 19.91 | 21.71 | 21.35 | 21.18 | 20.89 | 20.38 |
| 10 | ≈ 11.03 | ≈ 14.77 | 16.31 | 17.75 | 18.88 | 19.74 | 20.33 | 20.86 | 22.25 | 24.28 | 23.93 | 23.74 | 23.43 | 22.85 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.928 |
| SC2 | 0 | 8 | 16.475 |
| SC3 | -18 | 7 | 13.078 |
| SC4 | -25 | 6 | 10.491 |
| SC5 | -34 | 6 | 9.433 |
| A | 3348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 3035 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 3348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.