EG-A-225AD6-C25 C
1.47 kW
Defrost: None
Product code: EG-A-225BC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 848 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 5.7 m² |
| Inner volume | 0.9 dm³ |
| Fin spacing | 3.8 mm |
| Fin material | Aluminium |
| Net weight | 9 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.5 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø3/8" |
| EG-A-225BC4-C25 C | None |
|---|---|
| EG-A-225BC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.55 | 0.58 | 0.61 | 0.64 | 0.65 | 0.66 | 0.66 | 0.68 | 0.73 | 0.79 | 0.77 | 0.77 | 0.76 | 0.75 |
| 5 | 0.66 | 0.71 | 0.76 | 0.80 | 0.83 | 0.84 | 0.85 | 0.87 | 0.93 | 1.02 | 1.00 | 0.99 | 0.98 | 0.96 |
| 6 | ≈ 0.77 | 0.84 | 0.90 | 0.96 | 1.00 | 1.02 | 1.04 | 1.06 | 1.13 | 1.23 | 1.21 | 1.20 | 1.18 | 1.16 |
| 7 | ≈ 0.86 | 0.95 | 1.03 | 1.11 | 1.16 | 1.20 | 1.21 | 1.24 | 1.33 | 1.44 | 1.42 | 1.40 | 1.39 | 1.35 |
| 8 | ≈ 0.87 | ≈ 1.05 | 1.15 | 1.25 | 1.31 | 1.36 | 1.39 | 1.43 | 1.53 | 1.66 | 1.63 | 1.62 | 1.60 | 1.56 |
| 9 | ≈ 0.51 | ≈ 1.14 | 1.27 | 1.37 | 1.46 | 1.53 | 1.57 | 1.62 | 1.72 | 1.88 | 1.85 | 1.84 | 1.81 | 1.76 |
| 10 | ≈ 0.33 | ≈ 1.22 | 1.35 | 1.49 | 1.60 | 1.68 | 1.74 | 1.80 | 1.92 | 2.10 | 2.07 | 2.05 | 2.03 | 1.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.071 |
| SC2 | 0 | 8 | 1.430 |
| SC3 | -18 | 7 | 1.132 |
| SC4 | -25 | 6 | 0.902 |
| SC5 | -34 | 6 | 0.785 |
| A | 815 mm |
|---|---|
| B | 215 mm |
| C | 465 mm |
| F | 187 mm |
| E | 190 mm |
| D | 266 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø3/8" |
| Length | 815 mm |
|---|---|
| Width | 465 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.