EG-A-225AD6-C25 C
1.47 kW
Defrost: None
Product code: EG-A-325AB6-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,573 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 4.3 m² |
| Inner volume | 0.8 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 13 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| EG-A-325AB6-C25 C | None |
|---|---|
| EG-A-325AB6-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.59 | 0.56 | 0.55 | 0.54 | 0.52 | 0.51 | 0.50 | 0.51 | 0.54 | 0.58 | 0.56 | 0.55 | 0.55 | 0.53 |
| 5 | 0.81 | 0.78 | 0.77 | 0.76 | 0.74 | 0.72 | 0.70 | 0.71 | 0.75 | 0.81 | 0.78 | 0.77 | 0.76 | 0.74 |
| 6 | 1.03 | 1.02 | 1.01 | 1.00 | 0.99 | 0.96 | 0.94 | 0.94 | 1.00 | 1.07 | 1.03 | 1.01 | 0.99 | 0.97 |
| 7 | 1.25 | 1.25 | 1.26 | 1.27 | 1.26 | 1.23 | 1.20 | 1.21 | 1.27 | 1.36 | 1.30 | 1.28 | 1.25 | 1.21 |
| 8 | 1.43 | 1.45 | 1.47 | 1.49 | 1.50 | 1.50 | 1.49 | 1.49 | 1.57 | 1.69 | 1.61 | 1.59 | 1.55 | 1.48 |
| 9 | 1.61 | 1.65 | 1.68 | 1.71 | 1.72 | 1.72 | 1.71 | 1.72 | 1.83 | 1.98 | 1.91 | 1.89 | 1.85 | 1.79 |
| 10 | 1.78 | 1.84 | 1.88 | 1.93 | 1.95 | 1.95 | 1.95 | 1.96 | 2.07 | 2.24 | 2.17 | 2.14 | 2.10 | 2.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.171 |
| SC2 | 0 | 8 | 1.488 |
| SC3 | -18 | 7 | 1.263 |
| SC4 | -25 | 6 | 1.012 |
| SC5 | -34 | 6 | 1.031 |
| A | 1205 mm |
|---|---|
| B | 215 mm |
| C | 440 mm |
| F | 187 mm |
| E | 365 mm |
| D | 441 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 1205 mm |
|---|---|
| Width | 440 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.