EG-230AB4-C21 C
3.60 kW
Defrost: Electric
Product code: EG-230BB4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,611 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 11.8 m² |
| Inner volume | 2.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EG-230BB4-C21 C | None |
|---|---|
| EG-230BB4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.48 | 1.50 | 1.53 | 1.55 | 1.55 | 1.55 | 1.53 | 1.56 | 1.65 | 1.79 | 1.74 | 1.72 | 1.70 | 1.66 |
| 5 | 1.86 | 1.93 | 1.99 | 2.05 | 2.08 | 2.09 | 2.08 | 2.11 | 2.24 | 2.42 | 2.36 | 2.33 | 2.30 | 2.25 |
| 6 | 2.19 | 2.30 | 2.39 | 2.48 | 2.53 | 2.56 | 2.58 | 2.62 | 2.78 | 3.02 | 2.96 | 2.93 | 2.90 | 2.84 |
| 7 | 2.52 | 2.66 | 2.80 | 2.91 | 2.99 | 3.03 | 3.06 | 3.11 | 3.30 | 3.59 | 3.51 | 3.48 | 3.43 | 3.36 |
| 8 | 2.80 | 2.99 | 3.17 | 3.33 | 3.44 | 3.51 | 3.55 | 3.60 | 3.82 | 4.15 | 4.07 | 4.03 | 3.98 | 3.89 |
| 9 | 3.05 | 3.30 | 3.54 | 3.74 | 3.86 | 3.97 | 4.02 | 4.09 | 4.35 | 4.74 | 4.64 | 4.60 | 4.54 | 4.43 |
| 10 | ≈ 3.28 | 3.59 | 3.88 | 4.10 | 4.29 | 4.42 | 4.51 | 4.59 | 4.89 | 5.32 | 5.22 | 5.18 | 5.11 | 4.99 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.223 |
| SC2 | 0 | 8 | 3.595 |
| SC3 | -18 | 7 | 2.948 |
| SC4 | -25 | 6 | 2.391 |
| SC5 | -34 | 6 | 2.215 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.