EG-230AC7-C25 C
3.48 kW
Defrost: Electric
Product code: EG-230BB4-C25 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,309 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 11.8 m² |
| Inner volume | 2.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 29 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EG-230BB4-C25 C | None |
|---|---|
| EG-230BB4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.43 | 1.45 | 1.47 | 1.49 | 1.50 | 1.49 | 1.48 | 1.51 | 1.60 | 1.74 | 1.70 | 1.68 | 1.66 | 1.63 |
| 5 | 1.81 | 1.87 | 1.92 | 1.98 | 2.00 | 2.01 | 1.99 | 2.02 | 2.15 | 2.33 | 2.26 | 2.24 | 2.21 | 2.17 |
| 6 | 2.13 | 2.22 | 2.31 | 2.39 | 2.44 | 2.47 | 2.48 | 2.52 | 2.68 | 2.91 | 2.85 | 2.82 | 2.79 | 2.73 |
| 7 | 2.44 | 2.58 | 2.70 | 2.81 | 2.87 | 2.92 | 2.94 | 2.98 | 3.17 | 3.45 | 3.37 | 3.34 | 3.29 | 3.21 |
| 8 | 2.72 | 2.90 | 3.07 | 3.21 | 3.31 | 3.38 | 3.41 | 3.45 | 3.67 | 3.98 | 3.90 | 3.86 | 3.80 | 3.70 |
| 9 | 2.97 | 3.20 | 3.42 | 3.61 | 3.74 | 3.81 | 3.86 | 3.92 | 4.17 | 4.53 | 4.44 | 4.39 | 4.32 | 4.21 |
| 10 | ≈ 3.20 | 3.48 | 3.75 | 3.96 | 4.13 | 4.25 | 4.32 | 4.40 | 4.68 | 5.09 | 4.99 | 4.94 | 4.86 | 4.72 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.985 |
| SC2 | 0 | 8 | 3.454 |
| SC3 | -18 | 7 | 2.841 |
| SC4 | -25 | 6 | 2.311 |
| SC5 | -34 | 6 | 2.149 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.