EG-330AB4-C21 C
5.15 kW
Defrost: Electric
Product code: EG-230BE4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,121 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 23.6 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-230BE4-C21 C | None |
|---|---|
| EG-230BE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.17 | 2.22 | 2.27 | 2.31 | 2.33 | 2.32 | 2.30 | 2.36 | 2.51 | 2.73 | 2.66 | 2.64 | 2.62 | 2.58 |
| 5 | 2.70 | 2.80 | 2.89 | 2.97 | 3.01 | 3.02 | 3.00 | 3.05 | 3.24 | 3.52 | 3.41 | 3.37 | 3.31 | 3.22 |
| 6 | 3.17 | 3.33 | 3.47 | 3.60 | 3.68 | 3.71 | 3.71 | 3.77 | 4.00 | 4.34 | 4.20 | 4.14 | 4.06 | 3.92 |
| 7 | 3.59 | 3.81 | 4.01 | 4.18 | 4.29 | 4.35 | 4.36 | 4.43 | 4.70 | 5.10 | 4.95 | 4.89 | 4.79 | 4.63 |
| 8 | 4.02 | 4.30 | 4.55 | 4.77 | 4.92 | 4.99 | 5.01 | 5.09 | 5.40 | 5.85 | 5.68 | 5.61 | 5.49 | 5.29 |
| 9 | 4.38 | 4.73 | 5.05 | 5.33 | 5.52 | 5.63 | 5.67 | 5.75 | 6.10 | 6.61 | 6.42 | 6.33 | 6.19 | 5.96 |
| 10 | ≈ 4.70 | 5.13 | 5.52 | 5.87 | 6.11 | 6.23 | 6.30 | 6.40 | 6.79 | 7.36 | 7.16 | 7.06 | 6.91 | 6.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.160 |
| SC2 | 0 | 8 | 5.085 |
| SC3 | -18 | 7 | 4.234 |
| SC4 | -25 | 6 | 3.472 |
| SC5 | -34 | 6 | 3.209 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.