EG-425AC7-C23 C
4.59 kW
Defrost: None
Product code: EG-230BE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,806 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 23.6 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 33 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-230BE4-C25 C | None |
|---|---|
| EG-230BE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.99 | 2.02 | 2.05 | 2.08 | 2.09 | 2.09 | 2.07 | 2.12 | 2.26 | 2.45 | 2.39 | 2.37 | 2.35 | 2.32 |
| 5 | 2.47 | 2.54 | 2.61 | 2.67 | 2.70 | 2.70 | 2.68 | 2.72 | 2.89 | 3.14 | 3.04 | 3.01 | 2.96 | 2.88 |
| 6 | 2.92 | 3.04 | 3.15 | 3.25 | 3.31 | 3.33 | 3.31 | 3.35 | 3.56 | 3.85 | 3.73 | 3.68 | 3.61 | 3.49 |
| 7 | 3.32 | 3.49 | 3.65 | 3.78 | 3.87 | 3.92 | 3.93 | 3.98 | 4.22 | 4.58 | 4.45 | 4.39 | 4.29 | 4.13 |
| 8 | 3.72 | 3.94 | 4.12 | 4.30 | 4.43 | 4.49 | 4.51 | 4.57 | 4.84 | 5.25 | 5.11 | 5.04 | 4.94 | 4.77 |
| 9 | 4.07 | 4.35 | 4.61 | 4.83 | 4.98 | 5.06 | 5.09 | 5.16 | 5.47 | 5.93 | 5.77 | 5.69 | 5.58 | 5.37 |
| 10 | 4.38 | 4.73 | 5.05 | 5.33 | 5.52 | 5.63 | 5.68 | 5.75 | 6.10 | 6.61 | 6.44 | 6.35 | 6.21 | 5.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.438 |
| SC2 | 0 | 8 | 4.566 |
| SC3 | -18 | 7 | 3.825 |
| SC4 | -25 | 6 | 3.154 |
| SC5 | -34 | 6 | 2.948 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.