EG-430BC7-C21 C
7.58 kW
Defrost: Electric
Product code: EG-235BE7-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,289 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 21.7 m² |
| Inner volume | 6.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EG-235BE7-C21 C | None |
|---|---|
| EG-235BE7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.18 | 3.19 | 3.20 | 3.21 | 3.19 | 3.16 | 3.10 | 3.16 | 3.36 | 3.63 | 3.54 | 3.51 | 3.47 | 3.38 |
| 5 | 4.07 | 4.14 | 4.21 | 4.26 | 4.28 | 4.25 | 4.20 | 4.25 | 4.51 | 4.87 | 4.71 | 4.66 | 4.58 | 4.47 |
| 6 | 4.90 | 5.05 | 5.19 | 5.32 | 5.39 | 5.40 | 5.35 | 5.40 | 5.73 | 6.19 | 5.98 | 5.91 | 5.79 | 5.60 |
| 7 | 5.62 | 5.85 | 6.06 | 6.25 | 6.37 | 6.43 | 6.44 | 6.52 | 6.92 | 7.51 | 7.31 | 7.22 | 7.08 | 6.83 |
| 8 | 6.34 | 6.65 | 6.94 | 7.17 | 7.34 | 7.43 | 7.46 | 7.55 | 8.01 | 8.69 | 8.46 | 8.36 | 8.21 | 7.96 |
| 9 | 6.98 | 7.39 | 7.76 | 8.09 | 8.31 | 8.44 | 8.48 | 8.59 | 9.12 | 9.88 | 9.63 | 9.52 | 9.35 | 9.05 |
| 10 | 7.56 | 8.08 | 8.56 | 8.96 | 9.25 | 9.43 | 9.51 | 9.64 | 10.21 | 11.07 | 10.81 | 10.68 | 10.48 | 10.14 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.805 |
| SC2 | 0 | 8 | 7.548 |
| SC3 | -18 | 7 | 6.306 |
| SC4 | -25 | 6 | 5.191 |
| SC5 | -34 | 6 | 4.936 |
| A | 2097 mm |
|---|---|
| B | 685 mm |
| C | 310 mm |
| F | 630 mm |
| E1 | 893 mm |
| E | 1785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 2097 mm |
|---|---|
| Width | 685 mm |
| Height | 310 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.