EG-230AE4-C25 C
4.79 kW
Defrost: Electric
Product code: EG-325BE4-C23 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,687 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 26.6 m² |
| Inner volume | 4.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.4 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-325BE4-C23 C | None |
|---|---|
| EG-325BE4-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.08 | 2.14 | 2.19 | 2.24 | 2.27 | 2.28 | 2.27 | 2.31 | 2.46 | 2.67 | 2.61 | 2.58 | 2.55 | 2.50 |
| 5 | 2.55 | 2.65 | 2.74 | 2.83 | 2.88 | 2.90 | 2.89 | 2.93 | 3.11 | 3.38 | 3.29 | 3.25 | 3.19 | 3.10 |
| 6 | 2.97 | 3.13 | 3.27 | 3.39 | 3.47 | 3.52 | 3.52 | 3.57 | 3.78 | 4.11 | 3.99 | 3.94 | 3.87 | 3.74 |
| 7 | 3.36 | 3.56 | 3.75 | 3.92 | 4.03 | 4.10 | 4.12 | 4.18 | 4.44 | 4.81 | 4.69 | 4.63 | 4.55 | 4.39 |
| 8 | 3.74 | 4.00 | 4.24 | 4.43 | 4.59 | 4.67 | 4.71 | 4.78 | 5.07 | 5.50 | 5.36 | 5.30 | 5.20 | 5.02 |
| 9 | 4.07 | 4.39 | 4.69 | 4.95 | 5.14 | 5.26 | 5.30 | 5.38 | 5.71 | 6.19 | 6.04 | 5.97 | 5.85 | 5.64 |
| 10 | ≈ 4.36 | 4.75 | 5.12 | 5.44 | 5.67 | 5.82 | 5.90 | 5.99 | 6.33 | 6.87 | 6.71 | 6.63 | 6.50 | 6.27 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.707 |
| SC2 | 0 | 8 | 4.777 |
| SC3 | -18 | 7 | 3.972 |
| SC4 | -25 | 6 | 3.267 |
| SC5 | -34 | 6 | 3.010 |
| A | 1426 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 378 mm |
| E2 | 360 mm |
| E | 1115 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1426 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.