EG-430BE7-C25 C
8.56 kW
Defrost: Electric
Product code: EG-430AC4-C21 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,849 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 31.5 m² |
| Inner volume | 5.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 63 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.8 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø22 |
| EG-430AC4-C21 C | None |
|---|---|
| EG-430AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.47 | 3.64 | 3.78 | 3.90 | 3.97 | 4.00 | 3.99 | 4.08 | 4.34 | 4.71 | 4.60 | 4.57 | 4.52 | 4.45 |
| 5 | 4.21 | 4.46 | 4.69 | 4.89 | 5.02 | 5.11 | 5.15 | 5.25 | 5.59 | 6.08 | 5.96 | 5.92 | 5.85 | 5.74 |
| 6 | 4.92 | 5.27 | 5.59 | 5.87 | 6.07 | 6.18 | 6.25 | 6.37 | 6.78 | 7.38 | 7.23 | 7.17 | 7.07 | 6.91 |
| 7 | ≈ 5.52 | 5.99 | 6.43 | 6.81 | 7.09 | 7.24 | 7.35 | 7.49 | 7.97 | 8.68 | 8.51 | 8.43 | 8.32 | 8.12 |
| 8 | ≈ 6.06 | 6.65 | 7.21 | 7.65 | 8.02 | 8.28 | 8.44 | 8.62 | 9.18 | 10.01 | 9.82 | 9.73 | 9.59 | 9.35 |
| 9 | ≈ 6.54 | 7.26 | 7.87 | 8.48 | 8.95 | 9.30 | 9.52 | 9.75 | 10.39 | 11.33 | 11.13 | 11.04 | 10.88 | 10.60 |
| 10 | ≈ 4.30 | ≈ 7.81 | 8.54 | 9.27 | 9.86 | 10.29 | 10.59 | 10.87 | 11.59 | 12.65 | 12.45 | 12.35 | 12.18 | 11.86 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.454 |
| SC2 | 0 | 8 | 8.619 |
| SC3 | -18 | 7 | 6.935 |
| SC4 | -25 | 6 | 5.590 |
| SC5 | -34 | 6 | 4.996 |
| A | 3546 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø22 |
| Length | 3546 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.